Lenox P506640-01, Elite Series XP16 Units Heat Pumps Operating Gauge Set and Service Valves

Models: Elite Series XP16 Units Heat Pumps P506640-01

1 43
Download 43 pages 56.47 Kb
Page 4
Image 4
Operating Gauge Set and Service Valves

Operating Gauge Set and Service Valves

Manual background IMPORTANT

To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.

OPERATING SERVICE VALVES

The liquid and vapor line service valves are used for refrigerant recovery, flushing, leak testing, evacuating, weighing in refrigerant and optimizing system charge.

Each valve is equipped with a service port which has a factory−installed valve core. Figure 2 provides information on how to access and operate both angle− and ball−type service valves.

USING MANIFOLD GAUGE SET

When checking the system charge, only use a manifold gauge set that features low−loss anti−blow back fittings.

Manifold gauge set used for HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The manifold gauges should be rated for:

SHigh side

square inch gauge (psig)

SLow side sig with dampened speed to 500 psig

SManifold gauge set hoses must be rated for use to 800 psig of pressure with a 4000 psig burst rating.

Operating Angle−Type Service Valve:

1.Remove stem cap with an appropriately sized wrench.

2.Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back the stem out counterclockwise as far as it will go to open

the service valve.

 

SERVICE PORT CAP

TO INDOOR

 

 

 

 

UNIT

 

 

SERVICE PORT CORE

 

 

 

SERVICE PORT

 

 

TO OUTDOOR

 

CORE

(VALVE STEM SHOWN OPEN)

UNIT

VALVE STEM

 

INSERT HEX WRENCH HERE

 

SHOWN

 

 

 

 

 

 

 

 

CLOSED

2INSERT HEX−HEAD EXTENSION HERE

TO INDOOR Manual background

UNIT

TO OUTDOOR UNIT

STEM CAP

1 REMOVE

When service valve stem is in the CLOSED position,STEM CAP the service port is open to the line set and indoor unit.

When service valve is OPEN, the service port is open to line set, indoor and outdoor unit.

To Access Service Port:

Operating Ball−Type Service Valve:

1.Remove stem cap with an appropriately sized wrench.

2.Use an appropriately sized wrenched to open.

A service port cap protects the service port core from contamination and serves as the primary leak seal.

1.

Remove service port cap with an appropriately sized

 

wrench.

2.

Connect gauge set to service port.

1/6 TURN

11 12 1

10 2

98 Manual background543

A To open rotate stem

counterclockwise

TO INDOOR UNIT

3. When testing is completed, replace service port cap and

tighten as follows:

7 6

90°.

BTo close rotate stem

clockwise 90°.

SERVICE PORT SERVICE PORT CORE SERVICE PORT CAP

BALL (SHOWN CLOSED)

2 VALVE STEM

SWith torque wrench: Finger tighten and torque cap per table 1.

SWithout torque wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/6 turn clockwise.

 

 

 

 

 

1/12 TURN

Reinstall Stem Cap:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stem cap protects the valve stem from damage and

 

11

12 1

 

serves as the primary seal. Replace the stem cap and

 

2

tighten as follows:

10

 

 

 

 

 

 

S With Torque Wrench: Finger tighten and then

9

 

 

 

 

3

 

 

 

 

8

7

6

5

4

 

 

torque cap per table 1.

 

 

 

 

 

 

 

 

TO OUTDOOR UNIT

REMOVE

 

1 STEM CAP

SWithout Torque Wrench: Finger tighten and use an

appropriately sized wrench to turn an additional 1/12 turn clockwise.

NOTE

que.

Figure 2. Angle and Ball−Type Service Valves

Page 4

Page 4
Image 4
Lenox P506640-01, Elite Series XP16 Units Heat Pumps installation instructions Operating Gauge Set and Service Valves