Lenox P506640-01, Elite Series XP16 Units Heat Pumps installation instructions Defrost System

Models: Elite Series XP16 Units Heat Pumps P506640-01

1 43
Download 43 pages 56.47 Kb
Page 34
Image 34
Defrost System

Defrost System

This section addresses:

SEmergency Heat

SDefrost System Overview

SDefrost Control Connections, Jumper Settings and Features

SOperational Mode Overview (Calibration, Normal and Defrost)

SDefrost Cycle Actuation

EMERGENCY HEAT (AMBER LIGHT)

An emergency heat function is designed into some room thermostats. This feature is applicable when isolation of the outdoor unit is required, or when auxiliary electric heat is staged by outdoor thermostats. When the room thermostat is placed in the emergency heat position, the outdoor unit control circuit is isolated from power and field-provided relays bypass the outdoor thermostats. An amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat mode.

Emergency heat is usually used during an outdoor unit shutdown, but it should also be used following a power outage if power has been off for over an hour and the outdoor temperature is below 50°F (10°C). System should be left in the emergency heat mode at least six hours to allow the crankcase heater sufficient time to prevent compressor slugging.

DEFROST SYSTEM OVERVIEW

The control monitors ambient temperature, outdoor coil temperature, and total run time to determine when a defrost cycle is required. The coil temperature probe is designed with a spring clip to allow mounting to the outside coil tubing. The location of the coil sensor is important for proper defrost operation.

NOTE − The demand defrost control accurately measures the performance of the system as frost accumulates on the outdoor coil. This typically will translate into longer running time between defrost cycles as more frost accumulates on the outdoor coil before the demand defrost control initiates defrost cycles.

DEFROST CONTROL CONNECTIONS, JUMPERS SETTINGS AND FEATURES

Pressure Switch 5−Strike Lockout

The internal control logic of the demand defrost control counts the pressure switch trips only while the Y1 (Input) line is active. If a pressure switch opens and closes four times during a Y1 (Input), the control logic will reset the pressure switch trip counter to zero at the end of the Y1 (Input). If the pressure switch opens for a fifth time during the current Y1 (Input), the control will enter a lockout condition.

The 5−strike pressure switch lockout condition can be reset by cycling OFF the 24−volt power to the demand defrost control or by shorting the TEST pins between 1 to 2 seconds. All timer functions (run times) will also be reset.

If a pressure switch opens while the Y1 Out line is engaged, a 5−minute short cycle will occur after the switch closes.

Demand Defrost Control Pressure Switch

Connections

The unit’s automatic reset pressure switches (LO PS − S87 and HI PS − S4) are factory−wired into the demand defrost control on the LO−PS and HI−PS terminals, respectively.

Demand Defrost Control Sensors

Sensors connect to the demand defrost control through a field-replaceable harness assembly that plugs into the demand defrost control as illustrated in figure 1. Through the sensors, the demand defrost control detects outdoor ambient, coil, and discharge temperature fault conditions. As the detected temperature changes, the resistance across the sensor changes.

Testing Demand Defrost Control Sensors

Sensor resistance values can be checked by ohming across pins shown in table 11.

Table 11. Sensor Temperature /Resistance Range

 

 

 

Pins/W

 

Temperature

Resistance values

ire

Sensor

Range °F (°C)

range (ohms)

Color

 

 

 

 

Outdoor

−35 (−37) to 120 (48)

280,000 to 3750

3 & 4

 

 

 

(Black)

 

 

 

 

Coil

−35 (−37) to 120 (48)

280,000 to 3750

5 & 6

 

 

 

(Brown)

 

 

 

 

Discharge (if

24 (−4) to 350 (176)

41,000 to 103

1 & 2

applicable)

 

 

(Yellow)

 

 

 

 

Note: Sensor resistance increases as sensed temperature decreases.

Tables 12 and 13 shows how the resistance varies as the temperature changes for various types of sensors.

NOTE − When checking the ohms across a sensor, be aware that a sensor showing a resistance value that is not within the range shown in table 11, may be performing as designed. However, if a shorted or open circuit is detected, then the sensor may be faulty and the sensor harness will need to be replaced.

Defrost Temperature Termination Jumper

Settings (P1)

The demand defrost control selections are: 50, 70, 90, and 100°F (10, 21, 32 and 38°C). The shunt termination pin is factory set at 50°F (10°C). If temperature shunt is not installed, default termination temperature is 90°F (32°C).

Test Pins (P1) Function

Placing the jumper on the field test pins (P1) allows the technician to:

SClear short cycle lockout

SClear five−strike fault lockout

SCycle the unit in and out of defrost mode

SPlace the unit in defrost mode to clear the coil See figure 27 for flowchart of test pin (P1) operations.

Page 34

Page 34
Image 34
Lenox P506640-01, Elite Series XP16 Units Heat Pumps installation instructions Defrost System