System Operation

IMPORTANT

Some scroll compressor have internal vacuum protector that will unload scrolls when suction pressure goes below 20 psig. A hissing sound will be heard when the compressor is running unloaded. Protector will reset when low pressure in system is raised above 40 psig. DO NOT REPLACE COMPRESSOR.

This section addresses:

SUnit components (sensors, temperature switch, pressure switches and demand defrost control)

SSecond−stage operation

UNIT COMPONENTS

Demand Defrost Control (A108)

The demand defrost control measures differential temperatures to detect when the system is performing poorly because of ice build−up on the outdoor coil. The controller self−calibrates when the defrost system starts and after each system defrost cycle. The demand defrost control’s: components are shown in figure 25.

SDemand defrost control connections, jumpers and LED locations are shown in figure 25.

SDemand defrost control connections, jumpers and LED descriptions are listed on table 9.

SDemand defrost control status, fault and lockout LEDs are listed in table 10.

TEST PINS (P1)

DEFROST TERMINATION PIN SETTINGS (P1)

SENSOR PLUG IN (COIL AND AMBIENT SENSORS) (P4)

DELAY PINS (P5)

REVERSING VALVE (O OUT)

PRESSURE SWITCH CIRCUIT CONNECTIONS

LOW AMBIENT

THERMOSTAT PINS

(P3)

DIAGNOSTIC LEDS

(DS1 AND DS2)

24V TERMINAL STRIP

CONNECTIONS (P2)

Note − Component locations vary by board manufacturer.

Figure 25. Demand Defrost Control (A108)

Page 30

Page 30
Image 30
Lenox P506640-01, Elite Series XP16 Units Heat Pumps installation instructions System Operation, Unit Components