Lenox P506640-01 Adjusting Indoor Airflow, Optimizing System Refrigerant Charge

Models: Elite Series XP16 Units Heat Pumps P506640-01

1 43
Download 43 pages 56.47 Kb
Page 26
Image 26
Optimizing System Refrigerant Charge
3. Determine if fan needs adjustment

Optimizing System Refrigerant Charge

This section provides instructions on optimizing the system charge. This section includes:

SOptimizing procedure

SAdjusting indoor airflow

SUsing subcooling method

SApproved matched components, targeted subcooling (SC) values and add charge values

SNormal operating pressures

STemperature pressures

OPTIMIZING PROCEDURE

1.Move the low−side manifold gauge hose from the vapor line service valve to the true suction port (see figure 21).

2.Set the thermostat for either cooling or heating demand. Turn on power to the indoor unit and close the outdoor unit disconnect switch to start the unit.

3.Allow unit to run for five minutes to allow pressures to stabilize.

4.Check the airflow as instructed under Adjusting Indoor Airflow to verify or adjust indoor airflow for maximum

efficiency. Make any air flow adjustments before continuing with the optimizing procedure.

5.Use subcooling method to optimize the system charge (see figure 24). Adjust charge as necessary.

ADJUSTING INDOOR AIRFLOW

Heating Mode Indoor Airflow Check

(Only use when indoor unit has electric heat)

Indoor blower airflow (CFM) may be calculated by energizing electric heat and measuring:

STemperature rise between the return air and supply air temperatures at the indoor coil blower unit,

SMeasuring voltage supplied to the unit,

SMeasuring amperage being drawn by the heat unit(s).

Then, apply the measurements taken in the following formula to determine CFM:

Amps x Volts x 3.41

CFM =

1.08 x Temperature rise (F)

Cooling Mode Indoor Airflow Check

Check airflow using the Delta−T (DT) process using figure 23.

ADJUSTING INDOOR AIRFLOW

 

 

 

 

 

 

 

 

 

 

 

 

DT

 

 

 

 

 

 

 

 

Temp.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of air

 

 

80

24

24

24

23

23

22

22

 

22

20

19

18

17

16

15

 

entering

Dry−bulb

78

23

23

23

22

22

21

21

 

20

19

18

17

16

15

14

 

indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

76

22

22

22

21

21

20

19

 

19

18

17

16

15

14

13

 

 

 

 

 

coil ºF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

74

21

21

21

20

19

19

18

 

17

16

16

15

14

13

12

 

 

 

 

 

 

 

A

 

 

 

72

20

20

19

18

17

17

16

 

15

15

14

13

12

11

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7019 19 18 18 17 17 16 15 15 14 13 12 11 10

Wet−bulb ºF 57 58 59 60 61 62 63 64 65 66 67 68 69 70

1. Determine the desired DT

ature using dry bulb (A) and wet bulb (B). DT is the intersect- ing value of A and B in the table (see triangle).

2. Find temperature drop across coil

bulb entering and leaving air temperatures (A and C). Tem- perature Drop Formula: (TDrop) = A minus C.

ference between

 

 

B

 

C

TDrop

 

 

 

 

 

53º

19º

 

 

 

 

 

 

air flow

air flow

B

DRY

 

 

64º

BULB

 

 

 

All temperatures are

INDOOR

 

COIL

 

expressed in ºF

 

 

 

ADJUSTING INDOOR AIRFLOW A Manual background 72º

DRY

BULB

WET

BULB

the measured TDrop and the desired DT (TDropDT) is within +3º, no adjustment is needed. See examples: Assume DT =

15 and A temp. = 72º, these C temperatures would necessi- tate stated actions:

TDrop

DT

=

ºF

ACTION

53º

19

15

=

4

Increase the airflow

58º

14

15

=

−1

(within +3º range) no change

62º

10

15

=

−5

Decrease the airflow

4.Adjust the fan speed crease/decrease fan speed.

Changing air flow affects all temperatures; recheck tempera- tures to confirm that the temperature drop and DT are within +3º.

Figure 23. Checking Airflow over Indoor Coil Using Delta−T Formula

Page 26

Page 26
Image 26
Lenox P506640-01, Elite Series XP16 Units Heat Pumps Adjusting Indoor Airflow, Optimizing System Refrigerant Charge