Liebert 3000VA Manual Bypass Mode, Battery Mode, Battery Recharge Mode, Frequency Converter Mode

Models: GXT3 3000VA 700VA

1 44
Download 44 pages 44.14 Kb
Page 14
Image 14
1.5.2Manual Bypass Mode

Product Description

1.5.2Manual Bypass Mode

Manual Bypass Mode occurs when the Standby/Manual Bypass button is pressed and held for about 2 seconds while the Liebert GXT3 is in Mains (AC) Mode. Bypass operation is indicated by an audible alarm and illuminated amber bypass indicator. (If other indicators are illuminated, refer to 7.0 - Troubleshooting). During Bypass Mode, mains power bypasses the inverter and provides energy to the connected load.

NOTICE

Turning Off the UPS in Bypass Mode will result in loss of output power.

1.5.3Battery Mode

The Liebert GXT3 enters Battery Mode when mains power fails or is outside acceptable values. The battery system supplies power through the DC-to-DC converter to the inverter to generate clean AC power for the connected loads.

When the Liebert GXT3 enters Battery Mode, the UPS sounds a half-second beep at 10-second intervals. When approximately 2 minutes of run time remains, the beeps sound every 5 seconds to warn that the battery is getting low (this Low Battery Warning is user-configurable).

In Battery Mode, the AC Input indicator is Off and the Battery Level indicators illuminate to warn that a mains problem has occurred. Each battery level indicator represents a 20% capacity level. As capacity decreases, fewer indicators remain illuminated. Refer to 7.0 - Troubleshooting.

For approximate battery run times, refer to Table 15.

NOTICE

Turning Off the Liebert GXT3 when it is in Battery Mode will result in loss of output power. If the UPS is turned Off manually, it must be manually restarted after mains power returns.

If the UPS is turned Off by a communication signal or because the batteries are depleted, it will operate as selected in the configuration program for Auto-Restart (Refer to 5.2.1 - Configuration Program).

1.5.4Battery Recharge Mode

Once mains power is applied to the Liebert GXT3, the Battery Charger begins charging the batteries.

1.5.5Frequency Converter Mode

All models of the Liebert GXT3 are capable of frequency conversion. Frequency Conversion Mode can be selected using the configuration program. Allowable frequency operating modes include:

Auto Sensing - 50Hz or 60 Hz – Bypass Enabled

Auto Sensing - 50Hz or 60 Hz – Bypass Disabled

Frequency Converter - 50Hz – Bypass Disabled

Frequency Converter - 60Hz – Bypass Disabled

NOTE

The default for all models of the Liebert GXT3 is “Auto Sensing - 50Hz or 60 Hz – Bypass Enabled.”

! CAUTION

Do not touch the AC input receptacle when the UPS is operating. AC input voltages may still be present even when the AC input indicator is Off.

Liebert® GXT3

8

Page 14
Image 14
Liebert 3000VA, GXT3, 700VA user manual Manual Bypass Mode, Battery Mode, Battery Recharge Mode, Frequency Converter Mode