Installation
2.4.2Rack Installation
NOTE
• When the Liebert GXT3 is installed in a rack, the UPS must be supported by a shelf, brackets, or slide rails on each side. The
•Mounting hardware and slide rails are sold separately. Contact your local dealer or Emerson® representative for these options and any assistance.
To install a Liebert GXT3 UPS in a rack:
1.Unpack the two bracket assemblies and mounting hardware from the
(P/N:
2.Remove inner member of each bracket assembly by extending it to its outermost position, depressing the retaining latch and then pulling the inner member from the bracket assembly (see Figure 10).
Figure 10 Pulling inner member from each bracket assembly
|
|
|
| t |
|
|
| u | |
|
| o |
| |
| l |
|
| |
l |
|
| ||
u |
|
|
| |
P |
|
|
|
|
Bracket assembly
Retaining latch
Inner member
3.Determine the desired height and mounting position of the Liebert GXT3 inside the rack’s vertical rails.
! CAUTION
Reduce risk of tipping the rack by installing the Liebert GXT3 in the lowest possible rack position.
4. Attach the rear member of each bracket assembly to the rack’s vertical rails with two factory- supplied M5 screws (see Figure 11).
Liebert® GXT3™ | 12 |