Specifications

9.0SPECIFICATIONS

The specifications of the Liebert GXT3 are listed in Table 11 and Table 12.

Table 11 Specifications of GXT3-700RT230 and GXT3-1000RT230 UPS

 

 

Product model

Parameters

 

 

 

GXT3-700RT230

 

GXT3-1000RT230

 

 

 

 

Model Rating

700VA/630W

 

1000VA/900W

 

 

 

 

Dimensions, D x W x H, mm (in)

 

 

Unit

497 x 430 x 85 (19.6 x 16.9 x 3.3)

 

 

Shipping

617 x 570 x 262 (24.3 x 22.4 x 10.3)

 

 

 

 

Weight, kg (lb)

 

 

 

Unit

 

16.8 (37)

 

 

 

Shipping

 

20 (44)

 

 

 

 

Input AC

 

 

 

Voltage Range (typical)

230VAC nominal; variable based on output load

 

 

 

90% ~ 100% loading

 

177VAC/280VAC

 

 

 

70% ~ 90% loading

 

168VAC/280VAC

 

 

 

30% ~ 70% loading

 

150VAC/280VAC

 

 

 

0 ~ 30% loading

 

115VAC/280VAC

 

 

Frequency

40Hz ~ 70Hz; Auto Sensing

 

 

 

Input Power Receptacle

 

C14

 

 

 

 

Output AC

 

 

 

AC-AC Efficiency

 

> 88% AC-AC, minimum

 

 

 

Output Receptacles

 

C13 × 6

 

 

Voltage

220/230/240VAC (user configurable); ±3%

 

 

 

Frequency

 

50Hz or 60Hz

 

 

 

Waveform

 

Sine wave

 

 

Mains (AC) Mode Overload

200% for 2 seconds; 150% for 1 minute with transfer to bypass

 

 

 

 

Internal Battery Charger

 

 

 

Charger Current

 

1.3

 

 

 

 

Battery

 

 

 

Type

Valve-regulated, nonspillable, lead acid

 

 

 

Qty × V× Rating

 

4 × 12V × 5.0Ah

 

 

Battery Mfr/Part#

YUASA/NPH5-12; CSB/ HR 1221W; CSB/GP1245

 

 

Backup Time

See Table 15 - Battery run times

Recharge Time

3 hours to 90% capacity after full discharge with 100% load till UPS

auto-shutdown (Internal Batteries Only)

 

Environmental Requirements

 

 

 

Operating Temp

0ºC to +40ºC (+32ºF to +104ºF); Table 14 - Operating temperature parameters

Storage Temp

-15ºC to +50ºC (5ºF to 122ºF)

 

 

Relative Humidity

0%RH to 95%RH, non-condensing

 

 

Operating Elevation

Up to 3000m (10,000 ft.) at 25ºC (77ºF) without derating

 

 

Storage Elevation

15,240 (50,000 ft.) maximum

 

 

Audible Noise

< 46 dBA, at 1 meter (3.2ft) from the rear

< 43 dBA, at 1 meter (3.2ft) from the front or sides

 

Agency

 

 

 

Safety

IEC/EN/AS 62040-1:2008, GS mark

 

 

RFI/EMI

IEC/EN/AS 62040-2 2nd Ed (Category C2) = CISPR22 Class A

 

 

Surge Immunity

IEC/EN 62040-2 2nd Ed (IEC/EN 61000-4-5)

 

 

 

Transportation

 

ISTA Procedure 1A

33

Liebert® GXT3

Page 39
Image 39