2.0INSTALLATION

Installation

2.0INSTALLATION

2.1Unpacking and Inspection

Unpack the UPS and conduct the following checks:

Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and your local dealer or Emerson® representative immediately.

Check the accessories against the delivery list. If there is any discrepancy, contact your local dealer or your Emerson representative immediately.

2.2What’s Included

With GXT3 UPS

Terminal Block Communication terminals

Compact Disk with:

Liebert MultiLink®

Configuration Program

User Manual

USB Cable: one, 2m (6-1/2 ft.) long

Mounting hardware, including screws and handles

Plastic tower stand sets: 2 (four pieces)

Warnings, Safety Instructions booklet and WEEE recycling sheet (ISO 14001 compliance)

for 700VA - 1500VA: (2) 10A IEC C13 C14 Output Cable, 2m (6-1/2 ft.) long

for 2000VA - 3000VA:

(3) 10A IEC C13 C14 Output Cable, 2m (6-1/2 ft.) long

(1) CEE 7/7 (Schuko) to IEC C20 Input Cable, 2.5m (8-1/5 ft.) long

(1) BS1363 (UK) to IEC C20 Input Cable, 2.5m (8-1/5 ft.) long

NOTE

The GXT3 External Battery Cabinet shipping package includes one battery cabinet, two spacers for tower configuration and one DC power cable.

2.3Preparation for Installation

2.3.1Installation Environment

Install the UPS indoors in a controlled environment, where it cannot be accidentally turned Off. The installation environment should meet the specifications in 9.0 - Specifications.

Place the UPS in an area where airflow around the unit is unrestricted and away from water, flammable liquids, gases, corrosives and conductive contaminants. Avoid direct sunlight.

NOTE

Operating the Liebert GXT3 in temperatures above 25°C (77°F) reduces battery life.

Installation Clearances

Maintain a clearance of at least 100mm (4 inches) in the front and rear of the Liebert GXT3. Do not obstruct the air inlets on the front panel and rear panel of the UPS; blocking the air inlets reduces ventilation and heat dissipation, shortening the service life of the Liebert GXT3.