Specifications

Table 15 Battery run times

Number of

Load Percent

 

Run Time, Minutes

 

 

 

 

 

 

Batteries/Cabinets

of Capacity

700VA

1000VA

1500VA

2000VA

3000VA

 

 

 

 

 

 

 

 

10%

105

91

75

73

77

 

 

 

 

 

 

 

 

20%

62

38

35

33

37

 

 

 

 

 

 

 

 

30%

37

31

22

21

21

 

 

 

 

 

 

 

 

40%

32

23

16

15

15

 

 

 

 

 

 

 

Internal Battery

50%

27

17

11

11

11

 

 

 

 

 

 

60%

22

14

10

8

8

 

 

 

 

 

 

 

 

 

70%

18

11

6

6

6

 

 

 

 

 

 

 

 

80%

15

9

5

5

5

 

 

 

 

 

 

 

 

90%

13

8

4

4

4

 

 

 

 

 

 

 

 

100%

11

6

4

3

3

 

 

 

 

 

 

 

 

10%

307

214

194

166

182

 

 

 

 

 

 

 

 

20%

183

153

131

121

123

 

 

 

 

 

 

 

 

30%

150

124

96

79

79

 

 

 

 

 

 

 

 

40%

131

100

72

41

53

Internal Battery

 

 

 

 

 

 

50%

109

79

41

38

46

+ 1 External Battery

 

 

 

 

 

 

60%

98

66

38

34

38

Cabinet

 

70%

81

41

35

30

31

 

 

 

 

 

 

 

 

80%

72

38

32

25

26

 

 

 

 

 

 

 

 

90%

63

36

27

21

21

 

 

 

 

 

 

 

 

100%

41

34

23

17

18

 

 

 

 

 

 

 

 

10%

374

337

310

306

311

 

 

 

 

 

 

 

 

20%

314

216

185

159

160

 

 

 

 

 

 

 

 

30%

212

166

148

133

134

 

 

 

 

 

 

 

 

40%

186

152

126

105

105

Internal Battery

 

 

 

 

 

 

50%

160

136

103

81

81

+ 2 External Battery

 

 

 

 

 

 

60%

149

121

83

67

68

Cabinets

 

70%

139

104

72

40

52

 

 

 

 

 

 

 

 

80%

128

93

62

38

47

 

 

 

 

 

 

 

 

90%

112

79

40

36

43

 

 

 

 

 

 

 

 

100%

105

71

38

33

38

 

 

 

 

 

 

 

 

10%

480

480

339

331

335

 

 

 

 

 

 

 

 

20%

341

322

225

202

205

 

 

 

 

 

 

 

 

30%

319

219

184

157

157

 

 

 

 

 

 

 

 

40%

225

191

154

138

139

Internal Battery

 

 

 

 

 

 

50%

206

161

139

120

120

+ 3 External Battery

 

 

 

 

 

 

60%

187

151

123

99

100

Cabinets

 

70%

163

140

105

80

81

 

 

 

 

 

 

 

 

80%

155

128

93

70

71

 

 

 

 

 

 

 

 

90%

148

112

79

60

62

 

 

 

 

 

 

 

 

100%

141

105

71

40

51

 

 

 

 

 

 

 

Liebert® GXT3

36

Page 42
Image 42
Liebert GXT3, 700VA, 3000VA user manual Battery run times, Cabinet