Specifications

Table 15 Battery run times (continued)

Number of

Load Percent

 

Run Time, Minutes

 

 

 

 

 

 

Batteries/Cabinets

of Capacity

700VA

1000VA

1500VA

2000VA

3000VA

 

 

 

 

 

 

 

 

10%

480

480

480

346

480

 

 

 

 

 

 

 

 

20%

480

340

315

301

303

 

 

 

 

 

 

 

 

30%

338

316

215

186

187

 

 

 

 

 

 

 

 

40%

322

220

184

156

156

Internal Battery

 

 

 

 

 

 

50%

305

198

157

141

141

+ 4 External Battery

 

 

 

 

 

 

60%

217

166

145

126

127

Cabinets

 

70%

202

158

133

107

108

 

 

 

 

 

 

 

 

80%

186

149

120

95

97

 

 

 

 

 

 

 

 

90%

164

141

105

79

81

 

 

 

 

 

 

 

 

100%

159

133

96

72

73

 

 

 

 

 

 

 

The times above are approximate. They are based on new, fully charged batteries with 100% resistive loads and an ambient temperature of 77°F (25°C). To increase this time, turn Off non-essential loads (such as idle computers and monitors) or add optional external battery cabinets.