Specifications
Table 15 Battery run times (continued)
Number of | Load Percent |
| Run Time, Minutes |
| |||
|
|
|
|
| |||
Batteries/Cabinets | of Capacity | 700VA | 1000VA | 1500VA | 2000VA | 3000VA | |
|
|
|
|
|
|
| |
| 10% | 480 | 480 | 480 | 346 | 480 | |
|
|
|
|
|
|
| |
| 20% | 480 | 340 | 315 | 301 | 303 | |
|
|
|
|
|
|
| |
| 30% | 338 | 316 | 215 | 186 | 187 | |
|
|
|
|
|
|
| |
| 40% | 322 | 220 | 184 | 156 | 156 | |
Internal Battery |
|
|
|
|
|
| |
50% | 305 | 198 | 157 | 141 | 141 | ||
+ 4 External Battery |
|
|
|
|
|
| |
60% | 217 | 166 | 145 | 126 | 127 | ||
Cabinets | |||||||
| 70% | 202 | 158 | 133 | 107 | 108 | |
|
|
|
|
|
|
| |
| 80% | 186 | 149 | 120 | 95 | 97 | |
|
|
|
|
|
|
| |
| 90% | 164 | 141 | 105 | 79 | 81 | |
|
|
|
|
|
|
| |
| 100% | 159 | 133 | 96 | 72 | 73 | |
|
|
|
|
|
|
|
The times above are approximate. They are based on new, fully charged batteries with 100% resistive loads and an ambient temperature of 77°F (25°C). To increase this time, turn Off
9.1Product Warranty Registration
To register for warranty protection, visit the Quick Links section of the Liebert Web site at:
http://www.liebert.com
Click on Product Warranty Registration and fill in the form.
If you have any questions, contact Emerson® Channel Applications Engineering at:
North America:
Outside North America:
37 | Liebert® GXT3™ |