Communication
5.3Terminal Block Communication
The Terminal Block includes eight pins, as shown in Figure 20.
Figure 20 Terminal Block Communication pin layout
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
Any Mode Shut Down
Battery Mode Shut Down
Battery Mode
Low Battery
5.3.1Any Mode Shutdown
The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier, inverter and static switch so that there is no power to the loads.
Any Mode Shutdown can be operated locally or remotely:
•Local Any Mode Shutdown can be performed by shorting Pin 1 and Pin 2.
•Remote Any Mode Shutdown can be performed using a switch connected to Pin 1 and Pin 2 and mounted at a remote location.
NOTE
Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown, depending on the settings in the configuration program.