Maintenance
Figure 22 Disconnecting the battery plug and battery connector (front view)
|
|
|
|
Battery Connector | Battery Connector |
5.Grasp the battery handle and pull the internal battery pack out of the UPS, as shown in Figure 23.
Figure 23 Pulling out the battery
Internal Battery Pack
Battery
Handle
Pull Out with Battery Handle
6.Unpack the new internal battery pack. Take care not to destroy the packing.
Compare the new and old internal battery packs to make sure they are the same type and model. If they are the same, proceed with Step 7; if they are different, stop and contact your local Emerson® representative or Emerson Channel Support.
7.Line up and slide in the new internal battery pack.
8.Reconnect the battery plug and battery receptacle
9.Gently push the battery wire and internal battery pack back into the UPS.
10.Reattach the front battery door with the six screws.
11.Reattach the front plastic bezel cover to the UPS.
NOTE
The internal battery pack is
Do not replace the battery while the UPS is in Battery Mode. This will result in a loss of output power and will drop the connected load.
6.2Battery Charging
The batteries are
If the Liebert GXT3 will be stored for a long time, Emerson recommends connecting the UPS to input power for at least 24 hours every four to six months to ensure full recharge of the batteries.