Specifications

Table 13 Battery cabinet specifications

 

Model Number

 

Parameter

 

 

GXT3-48VBATT

 

GXT3-72VBATT

 

 

 

 

 

GXT3-700RT230, GXT3-1000RT230,

 

 

Used w/UPS Model

GXT3-1500RT230, GXT3-2000RT230

 

GXT3-3000RT230

Dimensions, D x W x H, mm (in)

 

 

 

 

 

Unit

497 × 430 × 85

 

602 × 430 × 85

(19.7 x 16.9 x 3.3)

 

(23.6 x 16.9 x 3.3)

 

 

Shipping

617 x 570 x 262

 

717 x 570 x 262

(24.3x 22.4 x 10.3)

 

(28.2 x 22.4 x 10.3)

 

 

Weight, kg (lb)

 

 

 

 

 

 

 

Unit

32 (70.5)

 

42 (92.6)

 

 

 

 

Shipping

35 (77.2)

 

46 (101.4)

 

 

 

 

Battery parameters

 

 

 

 

 

 

Type

Valve-regulated, nonspillable, lead acid

 

 

 

Qty × V× Rating

2 × 4 × 12V × 9.0Ah

 

2 × 6 × 12V × 9.0Ah

 

 

 

Battery Mfr/Part#

Panasonic/UP-RW1245 CSB/HR 1234W F2

 

 

Backup Time

See Table 15 - Battery run times

 

 

 

 

Environmental

 

 

 

 

 

 

Operating Temperature

0ºC to 40ºC (32ºF to 104ºF)

 

 

Storage Temperature

-15ºC to +40ºC (19ºF to 104ºF)

 

 

Relative Humidity

0% to 95%, non-condensing

 

 

Operating Elevation

Up to 3000m (10,000 ft.) at 40ºC (104ºF) without derating

 

 

Storage Elevation

15000m (50,000 ft.) maximum

 

 

 

 

Agency

 

 

 

 

 

 

Safety

IEC/EN/AS 62040-1:2008, GS mark

 

 

RFI/EMI

FCC Part 15, Class A=CISPR22 Class B

 

 

Surge Immunity

IEC 62040-2 2nd Ed.: 2006

 

 

 

Transportation

ISTA Procedure 1A

 

 

 

 

 

Table 14 Operating temperature parameters

Ambient Temperature,

25-30 (77-86)

30-35 (86-95)

35-40 (95-104)

°C (°F)

 

 

 

 

 

 

 

Maximum Output Power

 

 

 

Factor Derating

100%-93%

93%-86%

86%-79%

@ Maximum Load

 

 

 

35

Liebert® GXT3

Page 41
Image 41
Liebert 3000VA, GXT3, 700VA user manual Battery cabinet specifications, Operating temperature parameters