Section 3: Operation

SECTION 4 — GLOSSARY OF CONTROL FUNCTIONS includes a functional description of each delay.

Set Options Sub-menu (cont’d)

From the Set Units menu, press 4. SHUTDOWN to display the Shutdown on Alarm screen:

SHUTDOWN ON ALARM

01-Y 02-Y 03-Y 04-Y 05-Y 06-Y 07-Y 08-Y 1=YES O=NO E=NEXT

Beginning with unit 01, indicate 1 (Yes) or 0 (No) if the unit should shut down on alarm. When you have selected the shutdown status for the last unit, the RAC2-8 displays the Set Units menu.

When you have configured the delays, from the Set Units menu, press 5 to return to the Set Options Menu.

2. DELAYS

From the Set Options Sub-menu, press 2. DELAYS to display the Set Delays menu:

SET DELAYS MENU

 

1. ALARM

2.HOLD

3.UNIT RESTART

5.RETURN

From the Set Delays menu, press 1. ALARM to configure the Alarm Delay:

ENTER ALARM DELAY <10.0> XX.X MINUTES THEN PUSH ENTER PUSH CLEAR TO RETURN

Enter the desired time for the alarm delay. The default is 10 minutes. Press E to accept the new delay, then press C to return to the Set Delays menu.

From the Set Delays menu, press 2. HOLD to configure the Hold Delay:

ENTER HOLD DELAY <10.0> XX.X MINUTES THEN PUSH ENTER PUSH CLEAR TO RETURN

Enter the desired time for the hold delay. The default is 10 minutes. Press E to accept the new delay, then press C to return to the Set Delays menu.

10 User Manual (9/97)

Page 15
Image 15
Liebert RAC2-8 manual Delays