Section 3: Operation
From the Set Delays menu, press 3. UNIT RESTART to configure the
restart delay:
ENTER RESTART DELAY
<00.1> XX.X MINUTES
THEN PUSH ENTER
PUSH CLEAR TO RETURN
Enter the desired time for the restart delay. The default is 0.1 minutes.
Press Enter to accept the new delay, then press C to return to the Set
Delays menu.
When you have configured the delays, from the Set Delays menu, press
5 to return to the Set Options Sub-menu.
3. TEMP/HUM
From the Set Options Sub-menu, press 3. TEMP/HUM to display the
Set T/H menu:
SET T/H MENU
1.T/H ALARM POINTS
2.TEMP. STAGING
3.F/C 4.LOCK 5.EXIT
Set Options Sub-menu (cont’d)
The Set Temp/Hum and Temp Staging functions apply only to Zone 1.
The temperature and humidity inputs are from a separate remote sensor,
not from an operating unit.
From the Set T/H menu, press 1. T/H ALARM POINTS:
TEMP HI>75 LOW>65
HUM HI>60 LOW>40
<RANGE 50-90> 00=off
E=NEXT C=RETURN
Beginning with Temp Hi, enter the temperature and humidity alarm
points. The third line displays the range for the alarm limit you are
selecting. Press E to continue to the next point. When you have se t all
points, press C to return to the Set T/H menu.
From the T/H menu, press 2. TEMP. STAGING:
STAGING ON/OFF >OFF
NORMAL TEMP >72
SENSITIVITY >02
1=ON O=OFF E=NEXT
Beginning with Staging ON/OFF, configure each parameter. Press E at
the last parameter to return to the T/H menu.
From the T/H menu, press 3. F/C to configure degrees in Fahrenheit or
Celsius:
SELECT F/C <F>
Liebert RAC2-8 11