Section 3: Operation

From the Set Delays menu, press 3. UNIT RESTART to configure the restart delay:

ENTER RESTART DELAY <00.1> XX.X MINUTES THEN PUSH ENTER PUSH CLEAR TO RETURN

Enter the desired time for the restart delay. The default is 0.1 minutes.

Press Enter to accept the new delay, then press C to return to the Set

Delays menu.

When you have configured the delays, from the Set Delays menu, press 5 to return to the Set Options Sub-menu.

3. TEMP/HUM

From the Set Options Sub-menu, press 3. TEMP/HUM to display the

Set T/H menu:

SET T/H MENU

1.T/H ALARM POINTS 2.TEMP. STAGING

3.F/C 4.LOCK 5.EXIT

Set Options Sub-menu (cont’d)

The Set Temp/Hum and Temp Staging functions apply only to Zone 1. The temperature and humidity inputs are from a separate remote sensor, not from an operating unit.

From the Set T/H menu, press 1. T/H ALARM POINTS:

TEMP HI>75 LOW>65 HUM HI>60 LOW>40 <RANGE 50-90> 00=off

E=NEXT C=RETURN

Beginning with Temp Hi, enter the temperature and humidity alarm points. The third line displays the range for the alarm limit you are selecting. Press E to continue to the next point. When you have set all points, press C to return to the Set T/H menu.

From the T/H menu, press 2. TEMP. STAGING:

STAGING ON/OFF

>OFF

NORMAL TEMP

>72

SENSITIVITY

>02

1=ON

O=OFF

E=NEXT

 

 

 

 

 

 

Beginning with Staging ON/OFF, configure each parameter. Press E at the last parameter to return to the T/H menu.

From the T/H menu, press 3. F/C to configure degrees in Fahrenheit or

Celsius:

SELECT F/C <F>

Liebert RAC2-8 11

Page 16
Image 16
Liebert RAC2-8 manual Temp/Hum