Section 3: Operation

Setup Zones/Units Options

Press 2 from the Main Menu to display the Set Options menu. The following screens show the terminal display that enables you to configure the Options menu items.

NUMBER OF ZONES/NUMBER OF UNITS PER ZONE

RAC2-8 MAIN MENU

SET OPTIONS MENU

1.Set Number of Zones

2.Set Number of Units per Zone

3.Set Unit Status

4.Set Emergency Power Units

5.Set Unit Shutdown on Alarm

6.Set Unit Labels

7.Set Alarm Delay

8.Set Hold Delay

9.Set Restart Delay

<ESC> TO EXIT

CURRENT NUMBER OF ZONES = 1

ENTER NEW NUMBER (1-4) <ESC to quit> >2

CURRENT NUMBER OF ZONES = 2

ENTER NEW NUMBER (1-4) <ESC to quit> >

SET OPTIONS MENU

** SET NUMBER OF UNITS PER ZONE ** ZONE 1 = 4 UNITS

ZONE 2 = 0 UNITS

ZONE 3 = UNPROGRAMMED

ZONE 4 = UNPROGRAMMED

ENTER ZONE (1 - 2) <ESC to quit> >2 ZONE 2 has 0 UNITS

ENTER NEW NUMBER (2-8) <ESC to quit> >2

** SET NUMBER OF UNITS PER ZONE ** ZONE 1 = 4 UNITS

ZONE 2 = 2 UNITS

ZONE 3 = UNPROGRAMMED

ZONE 4 = UNPROGRAMMED

ENTER ZONE (1 - 2) <ESC to quit> >

SET OPTIONS MENU

Setup Zones/Units Options (cont’d)

Configure the number of zones and number of units as desired.

UNIT STATUS

SET OPTIONS

MENU

 

** SET UNIT

STATUS **

 

UNIT

LABEL ZONE

STATUS

-----------------------------------------------

1

01

1

RUNNING

 

 

 

 

18 User Manual (9/97)

Page 23
Image 23
Liebert RAC2-8 manual Number of ZONES/NUMBER of Units PER Zone, Setup Zones/Units Options cont’d, Unit Status