Section 3: Operation

Set Modem Options (cont’d)

Hang up on DTR on-off transition

Model 1200: SW1 up and SW10 down

Model 2400: &D3

Track status of carrier detect

Model 1200: SW6 up

Model 2400: &C1

Enable Auto-answer

Model 1200: SW5 up

Model 2400: S0=1

Setup Temp/Humid Options

Press 8 from the Main Menu to display the Setup Temp/Humid Options screen.

RAC2-8 MAIN MENU

** SET TEMP/HUMIDITY OPTIONS **

1.

High Temperature Alarm =

00

2.

Low Temperature Alarm

=

00

3.

High Humidity Alarm

=

00

4.

Low Humidity Alarm

=

00

5.

Temperature Staging

=

OFF

6.

Normal Temperature

=

70

7.

Sensitivity

= 02

 

 

8.

Temp Display (F/C)

=

F

9.

High Humidity Lockout

=

60

A. Low Humidity Lockout

=

00

<ESC> TO EXIT

High Temperature Alarm = (50-90) >80

** SET TEMP/HUMIDITY OPTIONS **

1.

High Temperature Alarm =

80

2.

Low Temperature Alarm

=

00

3.

High Humidity Alarm

=

00

4.

Low Humidity Alarm

=

00

5.

Temperature Staging

=

OFF

6.

Normal Temperature

=

70

7.

Sensitivity

= 02

 

 

8.

Temp Display (F/C)

=

F

9.

High Humidity Lockout

=

60

A. Low Humidity Lockout = 00

<ESC> TO EXIT

Temperature Staging = (ENTER 1 for ON, 0 for OFF) >ON

Setup Temp/Humid Options (cont’d)

Temperature and humidity options apply to Zone 1. The system inputs come from a remote temp/hum sensor. Each alarm can be disabled by entering 00 as the alarm trip-point. Temperature Staging turns on a Standby unit when the room temperature exceeds the Normal Temperature by the number of degrees entered in Sensitivity. Also note that temperature can be displayed in either degrees F or degrees C.

24 User Manual (9/97)