1Determine water heater location
Figure 1-3_Combustion Air Direct from Outside
1.If air is taken directly from outside the building with no duct, provide two permanent openings to the equipment room (see FIG.
(a)Combustion air opening, with a minimum free area of one square inch per 4000 Btu/hr input (5.5 cm2 per kW). This opening must be located within 12" (30 cm) of the bottom of the enclosure.
(b)Ventilation air opening, with a minimum free area of one square inch per 4000 Btu/hr input (5.5 cm2 per kW). This opening must be located within 12" (30 cm) of the top of the enclosure.
Figure 1-4_Combustion Air Through Ducts
12
2.If combustion and ventilation air is taken from the outdoors using a duct to deliver the air to the equipment room, each of the two openings should be sized based on a minimum free area of one square inch per 2000 Btu/hr (11 cm2 per kW) of input (see FIG.
IF NECESSARY FOR
TIGHT CONSTRUCTION
Figure 1-5_Combustion Air from Interior Space
3.If air is taken from another interior space, each of the two openings specified above should have a net free area of one square inch for each 1000 Btu/hr (22 cm2 per kW) of input, but not less than 100 square inches (645 cm2) (see FIG.
Figure
4.If a single combustion air opening is provided to bring combustion air in directly from the outdoors, the opening must be sized based on a minimum free area of one square inch per 3000 Btu/hr (7 cm2 per kW). This opening must be located within 12" (30 cm) of the top of the enclosure (see FIG.