13 | Troubleshooting (continued) |
| |||
|
|
| |||
Table 13D Troubleshooting Chart - Noisy System |
| ||||
|
|
|
| ||
FAULT |
| CAUSE | CORRECTIVE ACTION | ||
|
|
|
| ||
|
| - Supply gas problem. Natural gas pressures |
| ||
|
| should be between 4 inches w.c. and | • Refer to Section 7 - Gas Connections for detailed | ||
|
| 14 inches w.c. | LP gas pressures should | ||
|
| be between | 8 inches w.c. and | information concerning the gas supply. | |
|
|
| |||
|
| 14 inches w.c. |
|
| |
|
|
|
|
| |
|
|
|
| • Refer to the Gas Valve Adjustment Procedure on | |
|
| - Gas/air mixture problem. | page 69 of this manual for the proper gas valve setting. | ||
Noisy | Verify that the vent/air intake lengths do not exceed the | ||||
|
| ||||
|
| maximum listed in the General Venting section. | |||
Operation |
|
| |||
|
|
| |||
|
|
|
|
| |
|
|
|
| • Refer to page 56 in this manual for the burner removal | |
|
| - Dirty/damaged burner. | and inspection procedure. Clean or replace the burner | ||
|
|
|
| as necessary. | |
|
|
|
| ||
|
| - Low water flow through the heat exchanger. | • Refer to Section 6 - System Piping for minimum flow | ||
|
|
|
| rates. | |
|
|
|
| ||
|
| - Air in the piping system. | • Properly purge all air from the piping system. | ||
|
|
|
|
| |
|
| - Blown fuse. |
| • Replace fuse F5 on the control board, see page 58 of | |
|
|
| this manual. | ||
|
|
|
| ||
No Pump |
|
|
| ||
- Faulty pump. |
| • Replace pump. | |||
Operation |
|
|
| ||
- Faulty pump relay. | • Replace pump relay. | ||||
|
| ||||
|
|
|
| ||
|
| - Internal fault on control board. | • Replace main control board. | ||
|
|
| |||
Relief Valve | - System pressure exceeds relief valve | • Lower the system pressure below the 150 PSI rating of | |||
Opening | setting. |
| the supplied relief valve. | ||
|
|
|
|
|
61