Lochinvar SNR200-100 Troubleshooting, Fault, Description, Corrective Action, Temp O/Shoot, Progr

Models: SNA400-125 SNR150-100 SNA285-125 SNR200-100 SNA500-125

1 72
Download 72 pages 52.95 Kb
Page 66
Image 66
(continued)

TM

Installation & Service Manual

13 Troubleshooting

Table 13E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

 

CORRECTIVE ACTION

 

 

 

 

 

 

The temperature rise across

the heat

• Verify that the system is full of water and that all air

 

exchanger has exceeded the set

has been properly purged from the system.

 

 

 

 

 

parameters for the water heater.

 

• Verify that the water heater is piped properly into the

 

 

 

heating system. Refer to Section 6 - System Piping

 

 

 

for the proper piping methods for the Shield water

 

 

 

heater.

 

 

 

 

• Check for 120 VAC to the water heater pump motor

 

 

 

on a call for heat. If voltage is not present, check the

 

 

 

wiring back to the main control board. Replace the

 

 

 

main control board if necessary.

 

 

 

 

• If 120 VAC is present on a call for heat and the water

 

 

 

heater pump is not operating, replace the pump.

 

 

 

• Verify that the water heater pump is set to the proper

Temp O/Shoot

 

 

speed or that the pump is the proper size.

 

 

Reference Section 6 - System Piping for water heater

(continued)

 

 

 

 

pump specifications.

 

 

 

 

 

 

 

 

 

Heat exchanger outlet water temperature

• Verify that the system is full of water and that all air

 

has exceeded the maximum outlet water

has been properly purged from the system.

 

 

 

 

 

temperature.

 

• Verify that the water heater is piped properly into the

 

 

 

heating system. Refer to Section 6 - System Piping

 

 

 

for the proper piping methods for the Shield water

 

 

 

heater.

 

 

 

 

• Check for 120 VAC to the water heater pump motor

 

 

 

on a call for heat. If voltage is not present, check

 

 

 

wiring back to the main control board. Replace the

 

 

 

main control board if necessary.

 

 

 

 

• If 120 VAC is present on a call for heat and the water

 

 

 

heater pump is not operating, replace the pump.

 

 

 

• Replace the main control board.

 

 

 

 

 

 

Parameters

After downloading parameters from a

• Press the ENTER/RESET button on the

display

Progr

laptop, the main control board

must be

panel.

 

(will require a manual

reset.

 

 

 

 

 

reset once the condition

 

 

 

 

has been corrected. Press

 

 

 

 

the RESET button on the

 

 

 

 

display to reset.)

 

 

 

 

 

 

 

 

 

 

 

• Check condensate tube from unit to floor drain for

Blocked Drain

 

 

proper installation and obstructions.

 

 

 

 

 

SW

The blocked drain switch has

detected

• Inspect condensate trap for blockage.

Clean if

(will retry after 5

necessary.

 

excessive condensate build up inside the

 

minutes. RESET may be

 

 

unit.

 

• Check for loose wiring connection at wire harness

pressed after condition is

 

 

plug.

 

corrected.)

 

 

 

 

 

 

 

 

 

 

• Bad blocked drain switch. Replace switch.

 

 

 

 

 

 

Parameters 66 Progr

Page 66
Image 66
Lochinvar SNR200-100 Troubleshooting, Fault, Description, Corrective Action, Installation & Service Manual, Temp O/Shoot