Lochinvar SNA500-125, SNR200-100 3Sidewall direct venting, Installation & Service Manual

Models: SNA400-125 SNR150-100 SNA285-125 SNR200-100 SNA500-125

1 72
Download 72 pages 52.95 Kb
Page 20
Image 20
Prepare wall penetrations

TM

Installation & Service Manual

3Sidewall direct venting

Prepare wall penetrations

1.Use the factory supplied wall plate as a template to locate the vent and air intake holes and mounting holes.

Air pipe penetration:

a.Cut a hole for the air pipe. Size the air pipe hole as close as desired to the air pipe outside diameter.

Vent pipe penetration:

a.Cut a hole for the vent pipe. For either combustible or noncombustible construction, size the vent pipe hole with at least a 1/2 inch clearance around the vent pipe outer diameter:

4½ inch hole for 3 inch vent pipe

5½ inch hole for 4 inch vent pipe

Drill 3/16" diameter holes for inserting the plastic anchors into the wall.

2.Install the vent and air intake piping through the wall into the vent plate openings. Seal all gaps between the pipes and wall. Use RTV silicone sealant to seal the air pipe. Use the glue (cement/primer) listed in Table 2A on page 15 to seal the vent pipe.

3.Mount and secure the vent plate to the wall using stainless steel screws. Seal around the plate to the wall assuring no air gaps.

4.Assemble the vent cap to the vent plate (see FIG. 3-4A). Insert the stainless steel screws into the vent cap screw hole openings and securely attach the vent cap to the vent plate.

5.Seal all wall cavities.

Figure 3-4ASidewall Termination Assembly

 

AIR PIPING

VENT PIPING

 

 

VENT PLATE

WALL PLATE

VENT CAP

 

GALVANIZED

 

THIMBLE

 

Prepare wall penetrations (Alternate - Field Supplied Option)

1.Air pipe penetration:

a.Cut a hole for the air pipe. Size the air pipe hole as close as desired to the air pipe outside diameter.

2.Vent pipe penetration:

a.Cut a hole for the vent pipe. For either combustible or noncombustible construction, size the vent pipe hole with at least a 1/2 inch clearance around the vent pipe outer diameter:

4½ inch hole for 3 inch vent pipe

5½ inch hole for 4 inch vent pipe

b.Insert a galvanized metal thimble in the vent pipe hole as shown in FIG. 3-4B.

3.Use a sidewall termination plate as a template for correct location of hole centers.

4.Follow all local codes for isolation of vent pipe when passing through floors or walls.

5.Seal exterior openings thoroughly with exterior caulk.

Figure 3-4BAlternate Sidewall Termination Assembly w/Field Supplied Fittings

Termination and fittings

1.The air termination coupling must be oriented at least 12 inches above grade or snow line as shown in FIG. 3-1A, page 18.

2.Maintain the required dimensions of the finished termination piping as shown in FIG. 3-1A, page 18.

3.If using the alternate sidewall termination do not extend exposed vent pipe outside of the building more than what is shown in this document. Condensate could freeze and block vent pipe.

Figure 3-4ASidewall Termination Assembly 20 Termination and fittings

Page 20
Image 20
Lochinvar SNA500-125, SNR200-100 3Sidewall direct venting, Installation & Service Manual, Prepare wall penetrations