Lochinvar SNA500-125 Troubleshooting continued, Fault, Description, Corrective Action, Fan High

Models: SNA400-125 SNR150-100 SNA285-125 SNR200-100 SNA500-125

1 72
Download 72 pages 52.95 Kb
Page 65
Image 65
Fan High

TM

Installation & Service Manual

13 Troubleshooting (continued)

Table 13E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

The actual fan RPM is 30% higher than

• Vent/air intake lengths exceed the maximum allowed

 

what is being called for.

lengths. Refer to Section 2 - General Venting for

Fan High

 

proper lengths.

 

 

 

 

 

OR

 

• Check for obstruction or blockage in the vent/air

Fan Speed High

 

intake pipes or at terminations.

 

 

 

 

 

(will require a manual

 

• Check the wiring connections at the fan and at the

reset once the condition

 

 

main control board.

has been corrected. Press

 

 

 

 

 

 

the RESET button on the

 

• Replace the fan.

display to reset.)

 

• Replace the main control board.

 

 

 

 

 

Sensor Open

Either the heat exchanger inlet water, heat

• Check the sensors and their associated wiring.

(will require a manual

exchanger outlet water or tank temperature

Repair or replace the sensor or wiring if damaged.

reset once the condition

sensor has been disconnected.

• Measure the resistance of the sensors and compare

has been corrected. Press

 

S1 = Outlet Sensor

the resistance to the tables on page 60 of this

the RESET button on the

manual.

display to reset.)

S2 = Inlet Sensor

 

 

 

 

 

 

• Replace the sensor if necessary.

 

 

 

Sensor Shorted

Either the heat exchanger inlet water heat

• Check the sensors and their associated wiring.

(will require a manual

exchanger outlet water or tank temperature

Repair or replace the sensor or wiring if damaged.

sensor has been shorted.

 

 

 

 

reset once the condition

• Measure the resistance of the sensors and compare

 

has been corrected. Press

S1 = Outlet Sensor

the resistance to the tables on page 60 of this

the RESET button on the

S2 = Inlet Sensor

manual.

display to reset.)

 

• Replace the sensor if necessary.

 

 

 

 

 

External Limit

An optional remote limit switch is not

• Check function of remote devices.

Switch

making.

• Check for loose or misplaced jumper if external

(will retry after 5

 

 

limit switch is not installed.

minutes. RESET may be

 

 

 

 

 

 

pressed after condition is

 

 

 

 

 

corrected.)

 

 

 

 

 

 

 

 

 

The flue temperature has exceeded the set

• Inspect the heat exchanger. Reference page 57 of

 

parameters for the water heater.

this manual for the procedure on how to clean the

 

 

flue side of the heat exchanger.

 

 

• Inspect the flue sensor and associated wiring.

 

 

Measure the resistance of the flue sensor and

Temp O/Shoot

 

compare to Table 13C on page 60 of this manual.

 

Replace the sensor if necessary.

 

 

 

 

• Verify that the vent/air intake pipes are properly

 

 

installed and that there are no obstructions.

 

 

• Replace the main control board.

 

 

 

 

 

 

 

 

 

 

65

 

 

 

 

 

 

 

 

 