13 Troubleshooting (continued)
Table 13E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT |
| DESCRIPTION | CORRECTIVE ACTION | ||||||
|
|
|
|
|
| ||||
|
|
|
|
| • Inspect spark electrode and associated wiring for | ||||
|
|
|
|
| damage and connection. Reference page 56 of this | ||||
|
|
|
|
| manual for removal and cleaning procedures. | ||||
|
|
|
|
| Replace if necessary. | ||||
|
|
|
|
| • Check for proper electrical grounding of unit. | ||||
|
|
|
|
| • Check incoming supply gas pressure. Natural gas | ||||
|
|
|
|
| pressures should be between 4 - 14 inches w.c. and | ||||
|
|
|
|
| LP gas pressures should be between 8 - 14 | ||||
|
|
|
|
| inches w.c. Refer to Section 7 - Gas Connections for | ||||
|
|
|
|
| detailed information concerning the gas supply. | ||||
|
|
|
|
| • Verify that the plastic hose from the gas valve to the air | ||||
|
|
|
|
| inlet is connected and is not damaged. | ||||
|
|
|
|
| • Verify that the vent/air intake pipes are installed | ||||
|
|
|
|
| correctly and there are no obstructions. | ||||
|
|
|
|
| • Check for 24 VAC to the gas valve at the | ||||
No Flame |
|
|
|
| connection on the side of the main control board | ||||
|
|
|
| during the ignition attempt. If no voltage is present, | |||||
Running |
|
|
|
| replace the main control board. | ||||
(will require a manual | The unit | was | running | and lost the flame | • If 24 VAC is present at the main control board, check | ||||
reset once the | |||||||||
condition has been | signal. | This | condition | occurred four (4) | the wiring between the main control board and the gas | ||||
valve. Replace the wiring if necessary. Do not | |||||||||
corrected. Press the | straight times. |
|
| ||||||
|
| disconnect the wiring from the gas valve and attempt | |||||||
RESET button on the |
|
|
|
| |||||
|
|
|
| to measure voltage at that point. The main control | |||||
display to reset.) |
|
|
|
| |||||
|
|
|
| board can detect if the gas valve is not connected and | |||||
|
|
|
|
| |||||
|
|
|
|
| will display the GV / Relay Fail fault. | ||||
|
|
|
|
| • If 24 VAC is present, check the outlet of the valve to | ||||
|
|
|
|
| ensure the valve is flowing gas. With a manometer | ||||
|
|
|
|
| connected to the outlet tap of the gas valve, when the | ||||
|
|
|
|
| unit is in the prepurge period, there should be a | ||||
|
|
|
|
| negative pressure present. When the valve is | ||||
|
|
|
|
| energized a change in pressure should occur. If the | ||||
|
|
|
|
| pressure change does not occur, the gas valve is not | ||||
|
|
|
|
| opening. Replace the gas valve. | ||||
|
|
|
|
| • Inspect flame sensor and associated wiring. | ||||
|
|
|
|
| Reference page 56 of this manual for removal and | ||||
|
|
|
|
| cleaning procedures. Replace if necessary. | ||||
|
|
|
|
| • Inspect the burner. Reference page 56 of this manual | ||||
|
|
|
|
| for removal and cleaning procedures. Replace if | ||||
|
|
|
|
| necessary. | ||||
|
|
|
|
| • Replace the main control board. | ||||
|
|
|
|
|
| ||||
GV/Relay |
|
|
|
| • Ensure gas valve switch is ON (Models | ||||
|
|
|
| and | |||||
Fail |
|
|
|
| |||||
|
|
|
|
|
|
|
| ||
(will require a manual |
|
|
|
| • Check wiring harness connection at the gas valve and | ||||
reset once the | The main control board did not detect the | at the main control board. | |||||||
condition has been | gas valve. |
|
| • Replace the gas valve wire harness. | |||||
corrected. Press the |
|
|
|
| |||||
|
|
|
|
|
|
|
| ||
RESET button on the |
|
|
|
| • Replace the gas valve. | ||||
display to reset.) |
|
|
|
| • Replace the main control board. | ||||
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|