Lochinvar SNR200-100, SNA500-125 4Vertical direct venting, Vent/air termination – vertical

Models: SNA400-125 SNR150-100 SNA285-125 SNR200-100 SNA500-125

1 72
Download 72 pages 52.95 Kb
Page 26
Image 26
Prepare roof penetrations

TM

Installation & Service Manual

4Vertical direct venting

Vent/air termination – vertical

Prepare roof penetrations

1.Air pipe penetration:

a.Cut a hole for the air pipe. Size the air pipe hole as close as desired to the air pipe outside diameter.

2.Vent pipe penetration:

a.Cut a hole for the vent pipe. For either combustible or noncombustible construction, size the vent pipe hole with at least a 1/2 inch clearance around the vent pipe outer diameter:

4½ inch hole for 3 inch vent pipe

5½ inch hole for 4 inch vent pipe

b.Insert a galvanized metal thimble in the vent pipe hole.

3.Space the air and vent holes to provide the minimum spacing shown in FIG. 4-1, page 25.

4.Follow all local codes for isolation of vent pipe when passing through floors, ceilings, and roofs.

5.Provide flashing and sealing boots sized for the vent pipe and air pipe.

Termination and fittings

1.Prepare the vent termination coupling and the air termination elbow (FIG. 4-1) by inserting the bird screens provided with the water heater. Bird screens are provided for either 3" (Models SNR150-100 -- SNR200-100) or 4" (Models SNA285-125 -- SNA500-125) fittings.

2.The air piping must terminate in a down-turned 180° return bend as shown in FIG. 4-1. Locate the air inlet pipe no further than 2 feet from the center of the vent pipe. This placement avoids recirculation of flue products into the combustion air stream.

3.The vent piping must terminate in an up-turned coupling as shown in FIG. 4-1. The top of the coupling must be at least 1 foot above the air intake. The air inlet pipe and vent pipe can be located in any desired position on the roof, but must always be no further than 2 feet apart and with the vent termination at least 1 foot above the air intake.

4.Maintain the required dimensions of the finished termination piping as shown in FIG. 4-1.

5.Do not extend exposed vent pipe outside of building more than shown in this document. Condensate could freeze and block vent pipe.

Multiple vent/air terminations

1.When terminating multiple Shield water heaters, terminate each vent/air connection as described in this manual (FIG. 4-2).

Terminate all vent pipes at the same height ￿ WARNING and all air pipes at the same height to avoid

possibility of severe personal injury, death, or substantial property damage.

2. Place roof penetrations to obtain minimum clearance of 12 inches between edge of air intake elbow and adjacent vent pipe of another water heater for U.S. installations (see FIG. 4-2). For Canadian installations, provide clearances required by CSA B149.1 Installation Code.

3. The air inlet of a Shield water heater is part of a direct vent connection. It is not classified as a forced air intake with regard to spacing from adjacent water heater vents.

Figure 4-2Vertical Terminations with Multiple Water Heaters

Figure 4-3Alternate Vertical Terminations with Multiple Water Heaters

Manual background 26 Manual background

Page 26
Image 26
Lochinvar SNR200-100, SNA500-125 4Vertical direct venting, Vent/air termination – vertical, Installation & Service Manual