13 Troubleshooting
Table 13E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT | DESCRIPTION | CORRECTIVE ACTION | ||
|
|
| ||
| The outlet water temperature has exceeded | • Verify that the system is full of water and that all air | ||
| the fixed setting of the manual reset high | has been properly purged from the system. | ||
| limit. | • Verify that the water heater is piped properly into the | ||
|
| |||
|
| heating system. Refer to Section 6 - System Piping | ||
Manual Reset |
| for the proper piping methods for the Shield water | ||
| heater. |
|
| |
High Limit |
| • Check 120 VAC to water heater pump motor on a call | ||
(will require a manual |
| |||
| for heat. If voltage is not present, check wiring back | |||
reset once the condition |
| |||
| to the main control board. | |||
has been corrected. Press |
| |||
|
|
|
| |
the RESET button on the |
| • Replace the main control board if necessary. | ||
display to reset.) |
| • If 120 VAC is present on a call for heat and the water | ||
|
| |||
|
| heater pump is not operating, replace the pump. | ||
|
| • Check resistance of water sensors and compare to | ||
|
| Table 13B on page 60 of this manual. Replace | ||
|
| sensor if necessary. |
| |
|
|
| ||
| The actual fan RPM is 30% lower than what | • Vent/air intake lengths exceed the maximum allowed | ||
| is being called for. | lengths. | Refer to Section 2 - General Venting for | |
| proper lengths. |
| ||
Fan Low |
|
| ||
| • Check for obstruction | or blockage in the vent/air | ||
OR |
| |||
| intake pipes or at terminations. | |||
Fan Speed Low |
| |||
|
|
|
| |
(will require a manual |
| • Check the wiring connections at the fan and at the | ||
reset once the condition |
| main control board. |
| |
has been corrected. Press |
| • Replace the fan. |
| |
the RESET button on the |
|
| ||
|
|
|
| |
display to reset.) |
| • Replace the main control board. | ||
|
|
| ||
| Blown fuse. | • Replace fuse F4 on the control board, see page 58 | ||
| of this manual. |
| ||
|
|
| ||
|
|
| ||
|
| • Check the wiring connections to switch. Wires | ||
|
| should be connected to the common and normally | ||
|
| closed terminals. |
| |
|
| • Air intake lengths exceed the maximum allowed | ||
|
| lengths. Refer to Section 2 - General Venting for | ||
APS |
| proper lengths. |
| |
| • Check | for obstruction or blockage in the air | ||
Open |
| |||
| intake pipes or at terminations. | |||
(will require a manual |
| |||
|
|
|
| |
reset once the condition | Air pressure switch contacts are open. | • Check reference hoses connected to the air pressure | ||
has been corrected. Press |
| switch for blockage or obstruction. | ||
the RESET button on the |
| • Inspect | the burner. | Reference page 56 of this |
display to reset.) |
| |||
| manual for removal and cleaning procedures. | |||
|
| |||
|
| Replace if necessary. |
| |
|
| • Inspect the heat exchanger. Reference page 57 of | ||
|
| this manual for removal and cleaning procedures. | ||
|
| Replace if necessary. |
| |
|
| • Faulty air pressure switch. Replace switch. | ||
|
|
|
|
|
64