Lochinvar SNA400-125 Troubleshooting, Fault, Description, Corrective Action, Manual Reset, Open

Models: SNA400-125 SNR150-100 SNA285-125 SNR200-100 SNA500-125

1 72
Download 72 pages 52.95 Kb
Page 64
Image 64
Manual Reset

TM

Installation & Service Manual

13 Troubleshooting

Table 13E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

The outlet water temperature has exceeded

• Verify that the system is full of water and that all air

 

the fixed setting of the manual reset high

has been properly purged from the system.

 

limit.

• Verify that the water heater is piped properly into the

 

 

 

 

heating system. Refer to Section 6 - System Piping

Manual Reset

 

for the proper piping methods for the Shield water

 

heater.

 

 

High Limit

 

• Check 120 VAC to water heater pump motor on a call

(will require a manual

 

 

for heat. If voltage is not present, check wiring back

reset once the condition

 

 

to the main control board.

has been corrected. Press

 

 

 

 

 

the RESET button on the

 

• Replace the main control board if necessary.

display to reset.)

 

• If 120 VAC is present on a call for heat and the water

 

 

 

 

heater pump is not operating, replace the pump.

 

 

• Check resistance of water sensors and compare to

 

 

Table 13B on page 60 of this manual. Replace

 

 

sensor if necessary.

 

 

 

 

 

The actual fan RPM is 30% lower than what

• Vent/air intake lengths exceed the maximum allowed

 

is being called for.

lengths.

Refer to Section 2 - General Venting for

 

proper lengths.

 

Fan Low

 

 

 

• Check for obstruction

or blockage in the vent/air

OR

 

 

intake pipes or at terminations.

Fan Speed Low

 

 

 

 

 

(will require a manual

 

• Check the wiring connections at the fan and at the

reset once the condition

 

main control board.

 

has been corrected. Press

 

• Replace the fan.

 

the RESET button on the

 

 

 

 

 

 

display to reset.)

 

• Replace the main control board.

 

 

 

 

Blown fuse.

• Replace fuse F4 on the control board, see page 58

 

of this manual.

 

 

 

 

 

 

 

 

 

• Check the wiring connections to switch. Wires

 

 

should be connected to the common and normally

 

 

closed terminals.

 

 

 

• Air intake lengths exceed the maximum allowed

 

 

lengths. Refer to Section 2 - General Venting for

APS

 

proper lengths.

 

 

• Check

for obstruction or blockage in the air

Open

 

 

intake pipes or at terminations.

(will require a manual

 

 

 

 

 

reset once the condition

Air pressure switch contacts are open.

• Check reference hoses connected to the air pressure

has been corrected. Press

 

switch for blockage or obstruction.

the RESET button on the

 

• Inspect

the burner.

Reference page 56 of this

display to reset.)

 

 

manual for removal and cleaning procedures.

 

 

 

 

Replace if necessary.

 

 

 

• Inspect the heat exchanger. Reference page 57 of

 

 

this manual for removal and cleaning procedures.

 

 

Replace if necessary.

 

 

 

• Faulty air pressure switch. Replace switch.

 

 

 

 

 

High Limit 64 has been corrected. Press

Page 64
Image 64
Lochinvar SNA400-125 Troubleshooting, Fault, Description, Corrective Action, Installation & Service Manual, Manual Reset