8Field wiring

8Field wiring

 

TM

Installation & Service Manual

 

 

 

 

 

 

￿WARNING

NOTICE

￿CAUTION

ELECTRICAL SHOCK HAZARD – For your safety, turn off electrical power supply before making any electrical connections to avoid possible electric shock hazard. Failure to do so can cause severe personal injury or death.

Wiring must be N.E.C. Class 1.

If original wiring as supplied with the water heater must be replaced, use only type 105°C wire or equivalent.

The water heater must be electrically grounded as required by National Electrical Code ANSI/NFPA 70 – latest edition.

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.

Installation must comply with:

1.National Electrical Code and any other national, state, provincial, or local codes, or regulations.

2.In Canada, CSA C22.1 Canadian Electrical Code Part 1, and any local codes.

Power cord connection

This water heater is designed to operate with 120 VAC and 60 Hz power supply. If allowed by local codes, connect the power cord provided with the heater to a GFI protected outlet on a separate circuit and breaker. Ensure the circuit cannot be interrupted by a switch used to control lights or other appliances.

If local codes do not allow for the use of the power cord, remove the cord from the junction box found on the side of the control support bracket (FIG. 8-2) and attach conduit to the junction box. Route the wires out of the appliance to a GFI protected outlet on a separate circuit and breaker.

Low voltage connections

1.Route all low voltage wires through the knockouts in the rear of the water heater, as shown in FIG. 8-1.

2.Connect low voltage wiring to low voltage connection board as shown in FIG. 8-3 on page 40 of this manual and the water heater wiring diagram.

Figure 8-1Routing Field Wiring

LOW VOLTAGE

WIRING KNOCKOUTS

￿WARNING Use of an extension cord is NOT allowed. If a suitable electrical outlet is not within reach

of the supplied power cord, a new receptacle must be installed or the power cord must be replaced with hard conduit as described above.

Figure 8-2Remove Power Cable

JUNCTION BOX

Runtime contacts

The electronic control closes a set of dry contacts whenever the burner is running. This is typically used by Building Management Systems to verify that the water heater is responding to a call for heat.

Auxiliary device proving switch

1.When the operation of an external limit needs to be verified before the water heater fires, remove the jumper wire from terminals X & B and connect them to the contacts on the external limit (FIG. 8-3).

Alarm contacts

The electronic control closes another set of contacts whenever the water heater is locked out or the power is turned off. This can be used to turn on an alarm, or signal a Building Management System that the water heater is down. Note that the alarm contacts will close momentarily after each call for

heat.