13 Troubleshooting (continued)

TM

Installation & Service Manual

13 Troubleshooting (continued)

Table 13A Troubleshooting Chart - No Display

FAULT

CAUSE

 

 

CORRECTIVE ACTION

 

 

 

 

 

 

 

- No 120 VAC supplied to unit.

Check external line switch, fuse, or breaker.

 

 

 

• Check

wiring

harness

connection

between

display

 

 

 

board

and

main

control board. Connect

 

 

 

harness at both points.

 

 

 

No Display

 

 

 

 

 

 

 

 

- Bad display board.

Replace board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Bad main control board.

Replace the main control board.

 

 

 

 

 

 

 

- Blown fuse.

Replace fuse F3 on the main control board, see

 

 

 

page 58 of this manual.

 

 

 

 

 

 

 

 

 

 

- Tank temperature set point satisfied.

Review temperature setting.

 

 

No Burner

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

- Unit locked out on fault.

Consult display for specific fault.

Refer

to fault

 

 

 

 

descriptions on page 62 of this manual for corrective

 

 

 

actions.

 

 

 

 

 

 

 

 

 

 

- Flue sensor open.

Verify that the flue sensor is located in the flue outlet.

Unit Does Not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Modulate

 

Check wiring connections at the flue sensor.

 

Above 50%

 

 

 

 

 

 

 

 

 

Check the resistance of the flue sensor and compare

 

 

 

 

 

to Table 3C on page 60 of this manual.

 

 

 

 

 

 

 

 

 

 