Installation & Service Manual
13 Troubleshooting (continued)
Table 13A Troubleshooting Chart - No Display
FAULT | CAUSE |
|
| CORRECTIVE ACTION |
| |||
|
|
|
|
| ||||
| - No 120 VAC supplied to unit. | • | Check external line switch, fuse, or breaker. |
| ||||
|
| • Check | wiring | harness | connection | between | display | |
|
|
| board | and | main | control board. Connect | ||
|
|
| harness at both points. |
|
|
| ||
No Display |
|
|
|
|
|
|
|
|
- Bad display board. | • | Replace board. |
|
|
|
| ||
|
|
|
|
| ||||
|
|
|
|
|
| |||
| - Bad main control board. | • | Replace the main control board. |
|
| |||
|
|
|
| |||||
| - Blown fuse. | • | Replace fuse F3 on the main control board, see | |||||
|
|
| page 58 of this manual. |
|
|
| ||
|
|
|
|
|
| |||
| - Tank temperature set point satisfied. | • | Review temperature setting. |
|
| |||
No Burner |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Operation | - Unit locked out on fault. | • | Consult display for specific fault. | Refer | to fault | |||
| ||||||||
|
|
| descriptions on page 62 of this manual for corrective | |||||
|
|
| actions. |
|
|
|
|
|
|
|
|
| |||||
| - Flue sensor open. | • | Verify that the flue sensor is located in the flue outlet. | |||||
Unit Does Not |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Modulate |
| • | Check wiring connections at the flue sensor. |
| ||||
Above 50% |
|
|
|
|
|
|
|
|
| • | Check the resistance of the flue sensor and compare | ||||||
|
| |||||||
|
|
| to Table 3C on page 60 of this manual. |
| ||||
|
|
|
|
|
|
|
|
|
59