Intellizone Delay Timer
Section [065]: 010 to 255 seconds; Default = 48 seconds
Enter the desired
follows the Entry Delay 2 Timer of its assigned partition. To program the Entry Delay Timers, refer to Entry Delay 1 and Entry Delay 2 on page 13.
Delay Before Alarm Report Code Transmission
Sections [001] to [016]: Zones 1 to 16; option [7]
Option [7] OFF =Delay alarm transmission disabled (default) Option [7] ON =Delay alarm transmission enabled
This feature is commonly used with Entry Delay zones to reduce false alarms created by new users who may not disarm the system in time. This feature works as follows:
•When an alarm condition occurs on a zone with this option enabled, the console enables the bell/siren output, but does not report the alarm to the central station until the end of the Alarm Before Transmission Delay.
•During this period, disarming the system disables the bell/ siren output and cancels the report code transmission.
Alarm Transmission Delay
Section [075]: 001 to 255 seconds; 000 = Disabled; Default = 0 seconds
Enter the desired
Remote Panic Disarm Lock Delay
Section [078]: 001 to 255 seconds; 000 = Disabled; Default = 20 seconds
When a panic alarm is generated through the use of a remote control, the system cannot be disarmed by remote control during the Remote Panic Disarm Lock Delay.
Enter the desired
Force Zones
Sections [001] to [016]: Zones 1 to 16; Option [8]
Option [8] OFF =Force zone disabled
Option [8] ON =Selected zone is Force enabled (default)
Any open Force zones at the time of arming will be considered deactivated by the console. If during this period a deactivated zone is closed, the console will revert that zone to active status. Consequently, the console will generate an alarm if the zone is breached.
Fire zones cannot be programmed with the Force Zone option because the console will not bypass a Fire zone when the system is being Force armed.
Stay Delay Zones
Section [094]: Options [1]
Option [1] OFF =Stay Delay zone disabled (default) Option [1] ON =Stay Delay zone enabled
When a Stay Delay zone is armed using the Stay or Instant arming methods and the zone is triggered, an alarm will not generate until the programmed Stay Delay elapses. A zone defined as Stay Delay 1 follows the Entry Delay 1 Timer of its assigned partition. Likewise, a zone defined as Stay Delay 2
Zones 15 and 16 become Hardwire Zones
Section [095]: Options [1] and [2]
Option [1] OFF = Wireless zone 15 remains unchanged (default) Option [1] ON = Wireless zone 15 uses the
zone input 1
Option [2] OFF = Wireless zone 16 remains unchanged (default) Option [2] ON = Wireless zone 16 uses the
zone input 2
The Magellan console comes with two
•With section [095] option [1] ON, zone 15 is connected to zone input 1.
•With section [095] option [2] ON, zone 16 is connected to zone input 2.
EOL (End-Of-Line) Zones
Section [095]: Option [3]
Option [3] OFF = Hardwire zones 1 & 2 do not require EOL resistors (default)
Option [3] ON = Hardwire zones 1 & 2 require EOL resistors
This feature only applies to Magellan’s
If the hardwire detection devices connected to Magellan’s zone inputs 1 and 2 have input terminals that require 1K9 end of line resistors, enable (ON) section [095] option [3]. For details on using EOL resistors, refer to page 8.
16 | Reference & Installation Manual |