Alarm Options
Bell Cut-off Timer
Section [063]: 001 to 255 minutes; 000 = Disabled; Default = 4 minutes
After an audible alarm, the siren will stop upon disarming of the system or when the Bell
Wireless Transmitter Supervision Options
Section [094]: Options [6] and [7]
This feature determines how the Magellan console will react to a Supervision Loss trouble. Table 5 shows the different supervision loss combinations available and how the system will react when armed or disarmed.
Table 5: Wireless Transmitter Supervision Options
Options | Description | |
[6] | [7] |
|
|
|
|
OFF | OFF | Wireless transmitter supervision disabled |
OFF | ON | Trouble only (default) |
|
| System armed or disarmed: If a supervision loss |
|
| occurs on a zone, the console will display a trouble on |
|
| the LCD screen and send a report to the central |
|
| monitoring station. |
ON | OFF | Audible alarm when armed |
|
| System armed: If a supervision loss occurs on a zone, |
|
| the console will follow the zone's Alarm Types setting |
|
| (see page 15). |
|
| System disarmed: If a supervision loss occurs on a |
|
| zone, the console will display a trouble on the LCD |
|
| screen. |
ON | ON | Audible alarm |
|
| System armed: If a supervision loss occurs on a zone, |
|
| the console will follow the zone's Alarm Types setting |
|
| (see page 15). |
|
| System disarmed: It functions the same as Trouble |
|
| Only setting, except it will also generate an audible |
|
| alarm. |
|
|
|
Supervision Bypass Options
Section [094]: Option [8]
Option [8] OFF =No Supervision Loss if detected on a Bypassed Zone (default)
Option [8] ON =Generate Supervision Loss if detected on a Bypassed Zone
•When option [8] is OFF, the Wireless Transmitter Supervision Options (page 22) will follow the zone's bypass definition. This means the console will not perform any action if a Supervision Loss occurs on a bypassed zone.
•When option [8] is ON, the Wireless Transmitter Supervision Options (page 22) will ignore the bypass definition. This means the console will generate an incident as per the set Wireless Transmitter Supervision Option if a supervision loss occurs on a bypassed zone.
Tamper Recognition Options
Section [094]: Options [3] and [4]
This feature determines how the Magellan console will react to a zone tamper. Table 6 shows the different tamper recognition combinations available and how the system will react when armed or disarmed.
|
| Table 6: Tamper Recognition Options | |
Options |
| Description | |
[3] | [4] |
|
|
|
|
|
|
OFF | OFF |
| Tamper recognition disabled (default) |
OFF | ON |
| Trouble only |
|
|
| System armed or disarmed: If a tamper wiring failure |
|
|
| occurs on a zone, the console will follow the zone's |
|
|
| Alarm Types setting (see page 15) and send a report |
|
|
| to the central monitoring station. |
ON | OFF |
| Audible alarm when armed |
|
|
| System armed: If a tamper failure occurs on a zone, |
|
|
| the console will follow the zone's Alarm Types setting |
|
|
| (see page 15). |
|
|
| System disarmed: If a tamper failure occurs on a |
|
|
| zone, the console will follow the zone's Alarm Types |
|
|
| setting (see page 15) and send a report to the central |
|
|
| monitoring station. |
ON | ON |
| Audible alarm |
|
|
| System armed: If a tamper failure occurs on a zone, |
|
|
| the console will follow the zone's Alarm Types setting |
|
|
| (see page 15). |
|
|
| System disarmed: It functions the same as Trouble |
|
|
| Only setting, except it will also generate an audible |
|
|
| alarm. |
|
|
|
|
Tamper Bypass Options
Section [094]: Option [5]
Option [5] OFF =Ignore any tampers detected on a bypassed zone (default)
Option [5] ON = Generate tamper if detected on a bypassed zone
•When option [5] is ON, the Tamper Recognition feature (page 22) will ignore the zone’s bypass definition. This means the console will generate an incident as per the set Tamper Recognition option if a tamper occurs on a bypassed zone.
•When option [5] is OFF, the Tamper Recognition feature (page 22) will follow the zone's bypass definition. This means the console will ignore any tampers that occur on a bypassed zone.
Check-in Supervision Options
Section [103]: Options [1] to [8]; Zones 1 to 8; Default: All ON
Section [104]: Options [1] to [8]; Zones 9 to 16; Default: All ON
If enabled, Magellan can wait for each of its assigned wireless transmitters to send a status signal within a specified time (see