presence and functionality. If a device has not sent a signal within the specified time period, Magellan can generate a trouble, an alarm and/or transmit a report code to the central monitoring station as defined by the Wireless Transmitter Supervision Options (page 22). Sections [103] and [104] determine which zones will be supervised and which will not. Enable the option pertaining to the zone you wish Magellan to supervise.
Check-in Supervision Time
Section [096]: Option [7]
Option [7] OFF
Section [096] option [7] defines the time period that Magellan will expect a
Panic Alarms
Section [091]: Options [1], [2] and [3]
Option [1] OFF = Panic 1 (Emergency Panic) disabled (default) Option [1] ON = Panic 1 (Emergency Panic) enabled
Option [2] OFF = Panic 2 (Auxiliary Panic) disabled (default) Option [2] ON = Panic 2 (Auxiliary Panic) enabled
Option [3] OFF = Panic 3 (Fire Panic) disabled (default) Option [3] ON = Panic 3 (Fire Panic) enabled
Enable section [091] options [1], [2] and [3] to enable the system’s three Panic alarms. Each panic alarm is activated by pressing two keys simultaneously and holding them down for 2 seconds. See Table 7 on page 23 for the appropriate panic alarm keys. Whether these panic alarms will generate a silent or audible alarm is determined by section [091] options [4] to [6] (see Panic Alarm Types on page 23).
Table 7: Panic Alarm Keys
Keys to press | Panic Alarm Type | |
|
|
|
[1] and [3] | Panic 1 | (Emergency Panic) |
|
|
|
[4] and [6] | Panic 2 | (Auxiliary Panic) |
|
|
|
[7] and [9] | Panic 3 | (Fire Panic) |
|
|
|
Remote controls can also be programmed to generate panic alarms. See Programming the Remote Control’s Buttons on page 18 for more information on programming remote controls to generate panic alarms.
Panic Alarm Types
Section [091]: Options [4], [5] and [6]
Option [4] OFF =Panic 1 (Emergency Panic) is silent (default) Option [4] ON =Panic 1 (Emergency Panic) is audible
Option [5] OFF =Panic 2 (Auxiliary Panic) is silent (default) Option [5] ON =Panic 2 (Auxiliary Panic) is audible
Option [6] OFF =Panic 3 (Fire Panic) is silent (default) Option [6] ON =Panic 3 (Fire Panic) is pulsed
Options [4] to [6] represent the alarm types of panic alarms 1 to 3 respectively.
Silent Alarm: The Magellan console will emit a confirmation beep and transmit the appropriate Panic report code (if programmed in section [139]). The console will not enable its speaker or the system siren.
Audible Alarm: Same as the silent alarm except that the console will enable its speaker and system siren until a user cancels the alarm (disarms) with a valid access code or when the Bell
Pulsed Alarm (Fire Panic only): Same as the audible alarm except that the siren will be pulsed as shown in Figure 17 on page 14. Refer to Standard 24Hr. Fire Zones on page 14 for more information on a pulsed siren output.
Paradox Magellan Systems | 23 |