Magellan MG-6060 Panic Alarms, Check-inSupervision Time, Panic Alarm Types, Panic Alarm Keys

Models: MG-6060

1 48
Download 48 pages 39.41 Kb
Page 25
Image 25
Check-in Supervision Time

presence and functionality. If a device has not sent a signal within the specified time period, Magellan can generate a trouble, an alarm and/or transmit a report code to the central monitoring station as defined by the Wireless Transmitter Supervision Options (page 22). Sections [103] and [104] determine which zones will be supervised and which will not. Enable the option pertaining to the zone you wish Magellan to supervise.

Check-in Supervision Time

Section [096]: Option [7]

Option [7] OFF =Check-in supervision time = 24Hrs (default) Option [7] ON =Check-in supervision time = 80 minutes

Section [096] option [7] defines the time period that Magellan will expect a check-in status signal from the specified wireless transmitters as defined in the Check-in Supervision Options (page 22). If no signal is received within the check-in supervision time, Magellan’s reaction will be defined by the Wireless Transmitter Supervision Options (page 22).

Panic Alarms

Section [091]: Options [1], [2] and [3]

Option [1] OFF = Panic 1 (Emergency Panic) disabled (default) Option [1] ON = Panic 1 (Emergency Panic) enabled

Option [2] OFF = Panic 2 (Auxiliary Panic) disabled (default) Option [2] ON = Panic 2 (Auxiliary Panic) enabled

Option [3] OFF = Panic 3 (Fire Panic) disabled (default) Option [3] ON = Panic 3 (Fire Panic) enabled

Enable section [091] options [1], [2] and [3] to enable the system’s three Panic alarms. Each panic alarm is activated by pressing two keys simultaneously and holding them down for 2 seconds. See Table 7 on page 23 for the appropriate panic alarm keys. Whether these panic alarms will generate a silent or audible alarm is determined by section [091] options [4] to [6] (see Panic Alarm Types on page 23).

Table 7: Panic Alarm Keys

Keys to press

Panic Alarm Type

 

 

 

[1] and [3]

Panic 1

(Emergency Panic)

 

 

 

[4] and [6]

Panic 2

(Auxiliary Panic)

 

 

 

[7] and [9]

Panic 3

(Fire Panic)

 

 

 

Remote controls can also be programmed to generate panic alarms. See Programming the Remote Control’s Buttons on page 18 for more information on programming remote controls to generate panic alarms.

Panic Alarm Types

Section [091]: Options [4], [5] and [6]

Option [4] OFF =Panic 1 (Emergency Panic) is silent (default) Option [4] ON =Panic 1 (Emergency Panic) is audible

Option [5] OFF =Panic 2 (Auxiliary Panic) is silent (default) Option [5] ON =Panic 2 (Auxiliary Panic) is audible

Option [6] OFF =Panic 3 (Fire Panic) is silent (default) Option [6] ON =Panic 3 (Fire Panic) is pulsed

Options [4] to [6] represent the alarm types of panic alarms 1 to 3 respectively.

Silent Alarm: The Magellan console will emit a confirmation beep and transmit the appropriate Panic report code (if programmed in section [139]). The console will not enable its speaker or the system siren.

Audible Alarm: Same as the silent alarm except that the console will enable its speaker and system siren until a user cancels the alarm (disarms) with a valid access code or when the Bell Cut-off timer elapses (if enabled; see Bell Cut-off Timer on page 22).

Pulsed Alarm (Fire Panic only): Same as the audible alarm except that the siren will be pulsed as shown in Figure 17 on page 14. Refer to Standard 24Hr. Fire Zones on page 14 for more information on a pulsed siren output.

Paradox Magellan Systems

23

Page 25
Image 25
Magellan MG-6060 installation manual Panic Alarms, Check-inSupervision Time, Panic Alarm Types, Panic Alarm Keys