A

B

7.5'

1 x 90° elbow in horizontal plane = 3’ (914mm)

(2.3m)

 

 

A + B = 17' (5.2m) Max.

 

FP1238

Fig. 19 Maximum vent run with elbows.

For each 45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18” (457 mm). This does not apply if the 45° elbows are installed on the vertical part of the vent system.

The maximum number of elbow degrees in a system is 270°. (Fig. 20)

Vertical Sidewall Installation

Twist Lock Pipe

STEP 1

Locate vent opening on the wall. It may be necessary to first position the fireplace and measure to obtain hole location. Depending on whether the wall is combustible or noncombustible, cut opening to size. (Fig. 21)

For combustible walls first frame in opening.

Example:

 

 

 

 

Elbow 1

=

90°

 

Elbow 2

=

45°

4

Elbow 3

=

45°

Elbow 4

=

90°

 

 

 

 

 

 

Total angular variation

=

270°

 

1 + 2 + 3 + 4 = 270°

RDV4136 Series Direct Vent Gas Fireplace

NOTE: When using flex vent, the opening will have to be measured according to the 1/2” (13 mm) rise in 12” (305 mm) vent run.

Combustible Walls: (Fig. 21) Cut a 9³⁄”H x 9³⁄”W (240 x 240 mm) hole through the exterior wall and frame as shown.

Noncombustible Walls: (Fig. 21) Hole opening must be 7¹⁄” (190 mm) in diameter.

Vent Opening for Combustible Wall

9³⁄

(240mm)

 

 

 

 

 

 

Framing

9³⁄

 

 

Detail

 

 

 

(240mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fireplace Hearth

Opening for Noncombustible Wall

7¹⁄

(190mm)

VO584-100

Fig. 21 Locate vent opening on wall.

STEP 2

Measure wall thickness and cut zero clearance sleeve parts to proper length (MAXIMUM 12”/305 mm). Assem- ble sleeve and attach to firestop with #8 sheet metal screws (supplied). Install firestop assembly. (Fig. 22)

Zero clearance sleeve is only required for combustible walls.

Adjustable

Max. Length

12” (305mm)

Zero Clearance

 

Sleeve

 

 

#8 Screws (2)

#8 Screws

 

(2)

 

1

3

2

FP1239

 

#8 Screws

 

(2)

Firestop

 

Adjustable Zero Clearance Sleeve

ZCS101

Fig. 22 Adjustable zero clearance sleeve.

STEP 3

Place fireplace into position. (Fig. 23) Measure the verti-

Fig. 20 Maximum number of elbow degrees.

cal height (X) required from the base of the flue collars to the center of the wall opening.

10010618

15

Page 15
Image 15
Majestic Appliances RDV4136 installation instructions Vertical Sidewall Installation Twist Lock Pipe