Troubleshooting AF4000 Valve (continued)

RDV4136 Series Direct Vent Gas Fireplace

Troubleshooting AF4000 Valve (continued)

Pilot will not light/stay lit

Verify the gas supply is turned on.

 

Verify the receiver is receiving the signal from the transmitter by listening for a

 

beep from the receiver when ON is pressed on the transmitter. If you do not hear

 

a beep, ensure the module has learned the transmitter (see above).

 

Ensure the orange lead from the pilot assembly igniter is securely connected to

 

the terminal labeled “I” and the white lead from the flame rectification sensor is

 

securely connected to the terminal labeled “S” on the control module. (Fig. 45)

 

Make sure the orange and white leads from the module are securely connected to

 

the terminals labeled “PILOT” on the valve body. (Fig. 48)

 

Ensure the black GROUND wire is securely connected to an appropriate metal

 

portion of the valve or pilot assembly. A proper ground is essential to spark

 

igniter operation.

 

 

Make certain the pilot flame is in contact with the flame rectification sensor on the

 

pilot assembly. This valve is equipped with a pilot flame adjustment screw. (Fig.

 

48) If the pilot flame is too small it will not contact the flame rectification sensor

 

and will not complete the safety circuit.

Figure 47: AF4000 MOD Module End

8 Pin IPI

 

6 Volt DC Adapter

Connection

 

 

Power Connection

FP1764

28

10010618

Page 28
Image 28
Majestic Appliances RDV4136 Series Direct Vent Gas Fireplace, Troubleshooting AF4000 Valve continued, igniter operation