2. Installation
2.6 Setting up the RS485 link
General
For UPSs equipped with the PowerServices TelPac external version (see table section 2.3 "The various installation types"), communication between the UPS and the external unit is achieved via a RS485 link in
The link works using the
Standard practice is to add line bias at the network master and impedance matching at the end of the line on the slave side.
The line must only be biased at one point.
"Single-unit" type installation
The external unit is
Configuration of communication parameters (mode, rate, etc.) is carried out on the RS485 cards on the respective UPSs (see "Configuring the RS485 card for Comet" or "Configuring the RAUZ card for Galaxy").
UPS with JBUS/ | PowerServices |
RS485 card | Telpac |
◗ Slave number x | ◗ Master |
◗ Without bias | ◗ With bias |
Phone
Settings
JBUS / RS485
◗With impedance matching ◗ Without impedance matching
◗ 1200,8,N,1 | ◗ 1200,8,N,1 |
CD
UPS
A 5V B R+ R- T+ T-
TelPac
The RS485 shielded
Page 18 - 34003602EN/AB