PowerServices TelPac external unit (2 inputs + 4 extensions)

C

D

E

F

< 10m

Extension

2. Installation

Four similar inputs C, D, E, F are available inside the external unit on terminal block XM13.

To connect contacts to these four inputs, proceed as follows:

Remove the cover (partly unscrew the screws and pivot the cover).

Remove the card from the external unit (3 screws).

Feed the cable through the grommet. Connect the cable(s) to terminal block XM13 as shown in the figure opposite.

Terminal block XM13

Phone

JBUS / RS485

Settings

CD

A 5V B R+ R- T+ T-

UPS

TelPac

 

A 5V B

Replace the card in the external unit and fix it in place (3 screws).

Replace the cover.

PowerServices TelPac is now ready for the parameter setting stage required for Teleservice. Consult the Technical Support documentation. Lastly, move on to step 2 (see section 2.1 "Procedure").