1. Presentation

1.4 Technical data sheet

Functions

Parameters

Characteristics/Default values

Possible values

 

 

 

 

RS232 Port

◗Rate

◗9600

◗9600

 

◗Data bits

◗8

◗8

 

◗Stop bits

◗1

◗1

 

◗Parity

◗None

◗Even, odd

RS485 Port

◗Rate, bits, stop

◗1200, 8, 1

◗See technical support

 

◗Parity

◗None

documentation

 

◗Mode

◗2 wires

◗2 wires / 4 wires

 

◗Master / slave

◗Master

◗Master

 

◗Bias

◗With

◗With / without

 

◗Impedance matching

◗Without

◗With / without

 

◗Cable cross-section

◗0.08 - 0.6 mm2 (28/20 AWG)

 

Modem

◗Analogue

◗V.34/33.6 kbps

 

 

 

◗Error correction: V.42 LAPM and MNP 2-4

 

 

 

◗Data compression: V.42b and MNP5

 

 

◗Country

◗Works with 39 country profiles

 

 

 

◗European CTR21 compatibility

 

 

◗Protection

◗Line protection included

 

 

 

 

 

Contact inputs

◗Dry contacts

◗Normally open (NO)

◗NO / NC

 

 

0.08 - 0.6 mm2 (28/20 AWG)

 

 

◗Number

◗2 (card version)

◗0 to 2

 

 

◗2+4 (external version) 0.08 - 0.5 mm2 (28/20 AWG)

◗0 to 6

 

◗Distance

◗10m maximum

 

 

 

 

 

Power supply

◗Voltage

◗5V DC

 

(external version)

◗Current

◗1A

 

 

 

 

 

Comment: only MGE UPS SYSTEMS can be connected to the RS485 link.