MGE UPS Systems 100 installation manual Impedance matching and bias settings

Models: 100

1 30
Download 30 pages 36.99 Kb
Page 19
Image 19

2. Installation

Impedance matching and bias settings

If a specific adjustment is required on the RS485 link, see the settings on DIP switch SA1:

Phone

Settings

JBUS / RS485

OFF

ON

8

1

SA1

Master (fixed)

Two-wire link

Bias

Without impedance matching

CD

UPS

A 5V B R+ R- T+ T-

TelPac

Default position

Switch number

Function

Switch number

Function

 

 

 

 

1

T+ to R+ connection

5

R+ 0V bias

2

T- to R- connection

6

T- +5V bias

3

T+ 0V bias

7

T+ T- impedance matching

4

R+ R- impedance matching

8

R- +5V bias

 

 

 

 

Example: SA1.6 = ON, T- has a +5V bias,

SA1.6 = OFF, T- does not have a +5V bias.

34003602EN/AB - Page 19