SECTION 7 − OPERATING AUXILIARY EQUIPMENT

7-1. Generator Power Panel Receptacles

 

 

 

 

 

 

 

 

 

 

1

2

4

3

If unit does not have GFCI recep- tacles, use GFCI-protected exten- sion cord.

.Generator power decreases as weld current increases.

1 240 V AC Receptacle RC1

RC1 supplies 60 Hz single-phase power at weld/power speed. Maximum output is 5 kVA/kW (peak) or 4.5 kVA/kW (continu- ous).

2120 V 20 A AC Duplex Receptacle RC2

3120 V 20 A AC Duplex Receptacle RC3

RC2 and RC3 supply 60 Hz single-phase power at weld/power speed. Maximum output from RC2 or RC3 is 2.4 kVA/kW.

NOTICE − Do not parallel the two 120 VAC duplex receptacles.

4 Supplementary Protector CB1

CB1 protects the receptacles from over- load. If CB1 opens, the receptacles do not work. Move switch to the On position to re- set.

229 573-A

.If supplementary protector continues

to open, contact Factory Authorized Service Agent.

Combined output of all receptacles limited to 4.5 kVA/kW continuous rating of the generator (See Section 13 − Generator Power Guidelines).

EXAMPLE: If 10 A is drawn from each 120 volt duplex receptacle, only 8 A is available from the 240 V receptacle.

2 x (120 V x 10 A) + (240 V x 8 A) = 4.5 kVA/ KW.

OM-228 042 Page 30