2.Grounding bar (G)

MITSUBISHI

Manual background ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-12

Description of Figures 1.4, 1.5, and 1.6:

1.CPM - Circuit protector for control power supply.

2.Grounding bar (G)

3.External contact signal terminal block (FIGURE 1.6) - Terminal block to connect contact signal input/output lines to and from the external devices. Refer to Figure 2.15 section 2.4 for details.

4.RS232C communication connector (FIGURE 1.6) - Refer to Figure 2.18 section 2.5 for details.

5.Inverter start switch - This switch is used to transfer the UPS from static bypass to inverter during maintenance purposes. Transfers will lock-out if the bypass voltage is more than +12%,-12% of nominal.

*Uninterrupted switching is made at the time of synchronous operation. Switching is impossible at the time of asynchronous operation.

6.“INVERTER STOP” switch - This switch is used to transfer the UPS from inverter to static bypass during maintenance purposes. Do not operate it under normal operation. Transfers will lock-out if the bypass voltage is more than +12%,-12% of nominal.

*Uninterrupted switching is made at the time of synchronous operation. Switching is impossible at the time of asynchronous operation.

7.“FAULT RESET” switch (FOR SERVICE PERSONNEL ONLY) - This switch resets errors resulting from alarm conditions. (Do not operate this switch while inverter and converter are in operation.)

8.Maintenance (Set) button (FOR SERVICE PERSONNEL ONLY) - This switch sets the UPS menu parameters.

9.“Test mode” switch (FOR SERVICE PERSONNEL ONLY) - This switch changes system operation to the test-mode. (This switch should not be operated by personnel other than an Authorized Service Engineer).

10.“BOOT” switch (FOR SERVICE PERSONNEL ONLY) - This switch boots the processor in the main control circuit resulting from alarm conditions. (Do not operate this switch while inverter and converter are in operation).

MITSUBISHI ELECTRIC 9800A SERIES UPS

Page 18
Image 18
Mitsubishi 9800A Series technical manual Grounding bar G