Mitsubishi 9800A Series technical manual ELECTRIC AUTOMATION, INC. for setup information

Models: 9800A Series

1 70
Download 70 pages 33.43 Kb
Page 32
Image 32
ELECTRIC AUTOMATION, INC. for setup information.

MITSUBISHI

B)Input Contacts (for remote access of UPS) ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

2-11

NOTE: The UPS is equipped with a selectable output contact feature. The above alarms are the default settings. Contact MITSUBISHI

ELECTRIC AUTOMATION, INC. for setup information.

B)Input Contacts (for remote access of UPS)

External contacts are provided by the user of the UPS system. Terminal voltage at the UPS is 24Vdc. Provide external dry contact accordingly.

NOTE: Do not apply voltages to remote access input terminals. Damage to UPS may result.

Refer to Figure 2.17 for a typical wiring configuration. Although this figure applies to the remote start/stop terminals, the same wiring arrangement is used for emergency stop; battery liquid low; and battery temperature high.

FIGURE 2.17 Remote "Start" Contact Connections

UPS Cabinet

External to UPS

 

Cabinet

 

Relay

Start

 

Coil

Start

 

 

 

 

Switch

 

Common

4S

 

0.5S -

24 VDC

ON

 

OFF

 

Relay Coil current : 8.3mA

Use Momentary Switches Only

 

User supplied

Details of input contacts for remote access : TN2

Terminals 1 to 2 Remote "Inverter Start" input terminal (IN1)

Used to start inverter from a remote location. UPS must be programmed for remote operation. Refer to Operations Menu for procedure.

Terminals 3 to 4 Remote "Inverter Stop" input terminal (IN2)

Used to stop inverter from a remote location. UPS must be programmed for remote operation. Refer to Operations Menu for procedure.

Terminals 5 to 6 "Battery Temp. High" contact input (IN3)

Input fed by a thermocouple that monitors battery temperature. The converter float voltage level is reduced for battery over-temperature conditions. External thermocouple is user supplied

MITSUBISHI ELECTRIC 9800A SERIES UPS

Page 32
Image 32