Mitsubishi 9800A Series technical manual A Output Contacts for external alarm annunciation

Models: 9800A Series

1 70
Download 70 pages 33.43 Kb
Page 31
Image 31
A)Output Contacts (for external alarm annunciation)

MITSUBISHI

Details of output alarm contacts : TN1 ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

2-10

A)Output Contacts (for external alarm annunciation)

Output contacts consist of form Adry type contacts. Rated capacity of all output contacts is NEC Class2 (30Vdc/1Adc). All dry contacts should be operated at their rated values or lower. Figure 2.16 illustrates a typical installation. The external relay can also be a lamp, LED, computer, etc.

FIGURE 2.16 Control Wiring for External Contacts

UPS Cabinet

Terminals 1 to 2, 3 to 4 "UPS failure" contactTerminals 21 to 22, 23 to 24 "Battery Low Voltage" contact (OUT5) Terminal

Relay

ContactTerminal

External to UPS Cabinet

Relay

Coil

Terminals 29 through 40 "Spare" contact (OUT7 through OUT9) NEC Class 2 Power Source

User supplied

Details of output alarm contacts : TN1

Terminals 1 to 2, 3 to 4 "UPS failure" contact

Activated when a major fault has occurred with the system. Terminals 5 to 6, 7 to 8 "Load on Bypass" contact (OUT1)

Activated when the power is supplied from the static bypass input. Terminals 9 to 10, 11 to 12 "Load on Inverter" contact (OUT2)

Activated when the power is supplied by the inverter. Terminals 13 to 14, 15 to 16 "Battery Operation" contact (OUT3)

Activated when the battery is operating following an AC power failure. Terminals 17 to 18, 19 to 20 "Rectifier Operation" contact (OUT4)

Activated when the rectifier is operating.

Terminals 21 to 22, 23 to 24 "Battery Low Voltage" contact (OUT5)

Activated when the battery voltage drops below discharge end voltage level during inverter operation (i.e. During AC fail condition).

Terminals 25 to 26, 27 to 28 "Overload" contact (OUT6) Activated when an overload has occurred to the system.

Terminals 29 through 40 "Spare" contact (OUT7 through OUT9)

MITSUBISHI ELECTRIC 9800A SERIES UPS

Page 31
Image 31
Mitsubishi 9800A Series A Output Contacts for external alarm annunciation, Details of output alarm contacts TN1