MITSUBISHI |
| 9800A SERIES UPS |
| Page Number: | ||||
ELECTRIC | OWNERS / TECHNICAL MANUAL |
|
| |||||
|
|
|
|
|
|
| ||
UF305 | UPS CONTROL CIRCUIT | Control clock abnormality | CALL SERVICE | [2] | Major | Lit on | ||
| ERROR |
|
| ENGINEER |
|
|
| |
UF306 | UPS CONTROL CIRCUIT | Control power source circuit | CALL SERVICE | [2] | Major | Lit on | ||
ERROR |
| abnormality | ENGINEER | |||||
|
|
|
|
| ||||
|
|
|
|
|
|
| ||
UF309 | INVERTER VOLTAGE | Inverter output voltage abnormality | CALL SERVICE | [2] | Major | Lit on | ||
ABNORMAL |
| before inverter power supply | ENGINEER | |||||
|
|
|
|
| ||||
|
|
|
|
|
|
|
| |
UF352 | CONTROL POWER |
| Control circuit abnormality | CALL SERVICE | [1] | Minor | Flicker | |
SUPPLY ABNORMAL |
| ENGINEER | ||||||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| |
UF402 | 52S ABNORMAL |
| 52S not turned OFF, or 52S turned | CALL SERVICE | [2] | Major | Lit on | |
| OFF without any command | ENGINEER | ||||||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| |
UF403 | CB3 ABNORMAL |
| CB3 not turned OFF | CALL SERVICE | [2] | Major | Lit on | |
| (#2) | ENGINEER | ||||||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| |
|
|
| 52S not turned ON, or 52S turned | CALL SERVICE |
|
|
| |
UF451 | 52S ABNORMAL |
| ON without any command when | [1] | Minor | Flicker | ||
| ENGINEER | |||||||
|
|
| manual transfer |
|
|
| ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
UF452 | CB3 ABNORMAL |
| CB3 open | CALL SERVICE | [1] | Minor | Flicker | |
| ENGINEER | |||||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| ||
UF453 | 52L OPERATION ERR. | 52L operated abnormality | CHECK 52L | [2] | Major | Lit on | ||
|
|
|
|
|
|
|
| |
| AC INPUT VOLTAGE OUT | AC input voltage fell out of +/- 15% | CHECK INPUT |
|
|
| ||
UA801 | POWER | [1] | Alarm | - | ||||
OF RANGE |
| range | ||||||
|
| SOURCE |
|
|
| |||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
| INVERTER OVERLOAD |
| WARNING : |
|
|
| ||
UA806 | Overload exceeded 105% (Note 7) | DECREASE | [1] | Alarm | - | |||
> 100% |
| |||||||
|
|
| LOAD |
|
|
| ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
| INVERTER OVERLOAD |
| WARNING : |
|
|
| ||
UA808 | Overload exceeded 125% (Note 7) | DECREASE | [1] | Alarm | - | |||
> 125% |
| |||||||
|
|
| LOAD |
|
|
| ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
| INVERTER OVERLOAD |
| WARNING : |
|
|
| ||
UA809 | Overload exceeded 150% (Note 7) | DECREASE | [1] | Alarm | - | |||
> 150% |
| |||||||
|
|
| LOAD |
|
|
| ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
|
|
| Momentary | WARNING : |
|
|
| |
UA810 | INVERTER OVERLOAD | DECREASE | [1] | Alarm | - | |||
Inverter power. | ||||||||
|
|
| LOAD |
|
|
| ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
UA811 | OVERLOAD TRANS. |
| Overload transfer | - | [1] | Alarm |
| |
|
|
|
|
|
|
| ||
UA812 | BYPASS VOLTAGE OUT | Bypass voltage fell out of +/- 20% | CHECK | [1] | Alarm | - | ||
OF RANGE |
| range | BYPASS INPUT | |||||
|
|
|
|
| ||||
|
|
|
|
|
|
|
| |
UA813 | BYPASS PHASE |
| Phase rotation is inverted when | CHECK | [1] | Alarm | - | |
ROTATION ERROR |
| bypass voltage is normal | BYPASS INPUT | |||||
|
|
|
|
| ||||
|
|
|
|
|
|
|
| |
| BYPASS FREQUENCY | Bypass frequency fell out of | CHECK |
|
|
| ||
UA814 | inverter synchronization | [1] | Alarm | - | ||||
OUT OF RANGE |
| BYPASS INPUT | ||||||
|
| range |
|
|
| |||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
MITSUBISHI ELECTRIC 9800A SERIES UPS