MITSUBISHI | 9800A SERIES UPS | Page Number: |
ELECTRIC | OWNERS / TECHNICAL MANUAL |
D) External Battery Supply
Please refer to the following when installing and maintaining batteries:
1.The customer shall refer to the battery manufacturer's installation manual for battery installation and maintenance instructions.
2.The maximum permitted fault current from the remote battery supply, and the DC voltage rating of the battery supply
TABLE 3.3 Maximum Permitted Fault Current
UPS CAPACITY | DC VOLTAGE | MAXIMUM PERMITTED |
(kVA) | RATING (V) | FAULT CURRENT (A) |
|
|
|
|
|
|
100 | 480 | 25000 |
|
|
|
150 | 480 | 25000 |
|
|
|
225 | 480 | 25000 |
|
|
|
300 | 480 | 25000 |
|
|
|
375 | 480 | 25000 |
|
|
|
500 | 480 | 25000 |
|
|
|
750 | 480 | 25000 |
|
|
|
3.3Procedure for Cable Connections *
1.Confirm the capacity of the UPS being installed. Identify the input/output power terminal blocks as shown in the appropriate Figures 3.1 through
2.Connect the internal control wire and power wire.
(1)Control wire
1.CB2 NO Auxiliary to terminal TN2- 23, 24.
2.
(2)Power wire
a.) From user’s distribution panel
1.X1
2.X2
3.X3