MITSUBISHI

9800A SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

3-1

3.0INSTALLATION AND OPERATION

3.1Transportation and Installation

TABLE 3.1 How to transport and install the system

Transportation

Installation

 

 

Transport unit with forklift.

Using the pre drilled holes (4 - 24) in the

Carry with overhead crane using

UPS channel base, anchor the unit using

eyebolts provided.

appropriate hardware. (Not provided)

 

 

Note : Do not transport in a horizontal position. Cabinets must be maintained upright within +/- 15° of the vertical during handling.

3.2Installation Procedure

A)Note the load tolerance of the floor Refer to Table 3.2 for list of UPS weights.

TABLE 3.2 List of UPS weights

UPS Capacity (kVA)

100

 

150

225

 

300

 

375

500

750

Weight (lb.)

2100

 

2820

3310

 

4990

 

5250

6930

9655

 

 

 

 

 

 

 

 

 

 

B) Minimum clearance required for ventilation

 

 

 

 

 

Right side

25 mm (not required when sidecars are used)

 

 

Left side

25 mm (not required when sidecars are used)

 

 

Back side

0.0 mm

 

 

 

 

 

 

 

 

Top side

600 mm (for air flow)

 

 

 

 

 

C) Space requirement for routine maintenance

 

 

 

 

 

Allow for the following space at the time of installation.

 

 

 

Front

1000 mm 100kVA, 150kVA, 225kVA

 

 

 

 

1075 mm 300kVA, 375kVA, 500kVA, 750kVA

 

 

Sides

0.0 mm

 

 

 

 

 

 

 

 

Rear

0.0 mm

 

 

 

 

 

 

 

 

MITSUBISHI ELECTRIC 9800A SERIES UPS

Page 34
Image 34
Mitsubishi technical manual Mitsubishi 9800A Series UPS, Transportation and Installation, Installation Procedure