Mitsubishi 9800A Series technical manual Static Bypass Input, +/-1%

Models: 9800A Series

1 70
Download 70 pages 33.43 Kb
Page 20
Image 20
INPUT

MITSUBISHI

STATIC BYPASS INPUT ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-14

TABLE 1.3 Detail of Specifications

Rated Output kVA

100

 

150

 

225

 

300

 

375

 

500

 

750

Rated Output kW

80

 

120

 

180

 

270

 

338

 

450

 

675

 

 

 

AC

INPUT

 

 

 

 

 

 

 

 

Configuration

3 phase, 3 wire

 

 

 

 

 

 

 

 

 

Voltage

277/480 V, 346/600 V

+15% to -15%

 

 

 

 

 

Frequency

60 Hz +/-5%

 

 

 

 

 

 

 

 

 

 

 

Reflected Current THD

6% max. at 100% load;

9% max. at 50% load

 

 

 

 

 

STATIC BYPASS INPUT

 

 

 

 

 

Configuration

3 phase, 4 wire

 

 

 

 

 

 

 

 

 

Voltage

277/480 V, 346/600 V

+/-10%

 

 

 

 

 

 

Frequency

60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BATTERY

 

 

 

 

 

 

 

Type

Lead Acid

 

 

 

 

 

 

 

 

 

 

 

Ride Through

Application Specific

 

 

 

 

 

 

 

 

 

Nominal Voltage

480 Vdc

 

 

 

 

 

 

 

 

 

 

 

Minimum Voltage

400 Vdc

 

 

 

 

 

 

 

 

 

 

 

Number of Cells

240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC OUTPUT

 

 

 

 

 

 

 

Configuration

3 phase, 4 wire

 

 

 

 

 

 

 

 

 

Voltage

277/480 V, 346/600 V

 

 

 

 

 

 

 

 

 

Voltage Stability

+/-1%

 

 

 

 

 

 

 

 

 

 

 

 

Frequency

60 Hz

 

 

 

 

 

 

 

 

 

 

 

Frequency Stability

+/-0.05% in free running mode

 

 

 

 

 

 

 

Power Factor

0.8 nominal

 

 

 

 

0.9 nominal

 

 

 

 

 

Power Factor range

0.8 to 1.0 lagging (within output

kW rating)

 

 

 

 

 

Voltage THD

2% maximum THD at 100% Linear Load

 

 

 

 

 

 

5% maximum THD at 100% non-linear load

 

 

 

 

 

Transient Response

+/-2% maximum at 100% load step

 

 

 

 

 

 

+/-1% maximum at loss/return of AC power

 

 

 

 

 

 

+/-5% maximum at load transfer to/from static bypass

 

 

 

Transient Recovery

Less than 20ms

 

 

 

 

 

 

 

 

 

Voltage Unbalance

1% maximum at 100% unbalanced load

 

 

 

 

 

Phase Displacement

1deg. maximum at 100% load

 

 

 

 

 

 

 

Inverter Overload

125% for 10 minutes; 150% for 1 minute

 

 

 

 

 

System Overload

1000% for 1 cycle

 

 

500% for 1 cycle

 

 

 

 

(with bypass available)

 

 

(with bypass available)

 

 

 

Bypass Overload

125% for 10 minutes

 

 

 

 

 

 

 

 

 

Withstand Rating

65kA*

 

 

 

 

 

 

* : with optional fuse

 

 

 

 

ENVIRONMENTAL

 

 

 

 

 

Cooling

Forced Air

 

 

 

 

 

 

 

 

 

 

 

Operating Temperature

32F to 104F ( 0C to 40C).

 

 

 

 

 

 

 

 

Recommended : 68F to 86F ( 20C to 30C)

 

 

 

 

 

Relative Humidity

5% ~ 95% Non Condensing

 

 

 

 

 

 

 

Altitude

0 to 9000 feet No Derating

 

 

 

 

 

 

 

Location

Indoor (free from corrosive gases and dust)

 

 

 

 

 

Paint Color

Munsell 5Y7/1 (Beige)

 

 

 

 

 

 

 

 

 

MITSUBISHI ELECTRIC 9800A SERIES UPS

Page 20
Image 20
Mitsubishi 9800A Series technical manual Static Bypass Input, +/-1%