UA817 | EMERGENCY STOP |
| Emergency stop applied | - | - | Alarm |
| - |
ACTIVATED |
|
| ||||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
UA819 | REMOTE START |
| There is an error with the remote | CALL SERVICE | [1] | Alarm |
| - |
BUTTON ABNORMAL | start switch. | ENGINEER |
| |||||
|
|
|
|
| ||||
|
|
|
|
|
|
|
| |
UA820 | REMOTE STOP BUTTON | There is an error with the remote | CALL SERVICE | [1] | Alarm |
| - | |
ABNORMAL |
| stop switch. | ENGINEER |
| ||||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
UA824 | CB2 OPEN |
| Battery disconnect circuit breaker | TURN ON CB2 | [1] | Alarm |
| - |
| CB2 turned OFF |
| ||||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
UA831 | EMERGENCY BYPASS | Emergency bypass switch turned | - | [1] | Alarm |
| - | |
SWITCH ON |
| to <Emergency> |
| |||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| BATTERY DEPLETED | DC voltage dropped below |
|
|
|
|
| |
UA834 | discharge end during inverter | - | - | Alarm |
| - | ||
INV. STOPPED |
|
| ||||||
|
| operation |
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
UA841 | CONVERTER OPE. |
| Converter operation interlock | - | - | Alarm |
| - |
PROHIBITION |
| applied |
| |||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
UA842 | OUTPUT CIRCUIT |
| Load bus voltage sensor | - | - | Alarm |
| - |
ABNORMAL |
| abnormality |
| |||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
#1: It has the possibility that output