This UPS does not include a Bypass input circuit breaker (MCCB) to protect bypass circuit. The Bypass input circuit breaker (MCCB) is to be field supplied and installed. Recommended Breaker (MCCB)'s Specifications are as follows:

MITSUBISHI

Manual background ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-2

WARNING 2

This UPS does not include a Bypass input circuit breaker (MCCB) to protect bypass circuit. The Bypass input circuit breaker (MCCB) is to be field supplied and installed. Recommended Breaker (MCCB)'s Specifications are as follows:

Capacity (kVA)

Bypass Voltage (Vac)

Bypass Rating (Aac)

Breaker (A)

100

480

120

150

 

 

 

 

 

600

96

125

 

 

 

 

150

480

180

225

 

 

 

 

 

600

144

200

 

 

 

 

225

480

271

350

 

 

 

 

 

600

217

300

 

 

 

 

300

480

361

500

 

 

 

 

 

600

289

400

 

 

 

 

375

480

451

600

 

 

 

 

 

600

361

500

 

 

 

 

500

480

601

800

 

 

 

 

 

600

481

600

 

 

 

 

750

480

902

1200

 

 

 

 

 

600

722

900

 

 

 

 

AC input and AC output overcurrent protection and disconnect devices shall be field supplied and installed. The DC output MCCB shall be field supplied and installed. The overcurrent protection device should be installed in the Battery cabinet and rated as indicated in TABLE 1.4.