MITSUBISHI | 9800A SERIES UPS | Page Number: |
ELECTRIC | OWNERS / TECHNICAL MANUAL |
TABLE 1.4 Rating of Contactors and Fuses
| NUMBER | APPLICATION |
|
|
|
|
| OUTPUT CAPACITY OF EQUIPMENT |
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
| 100kVA | 150kVA | 225kVA | 300kVA | 375kVA | 500kVA | 750kVA | ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| 480V | 600V | 480V | 600V | 480V |
| 600V | 480V |
|
| 600V | 480V |
| 600V | 480V | 600V | 480V | 600V | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| CB1 | AC input contactor | 135A | 200A | 350A | 450A | 660A | 660A | 910A | ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
| CB2 | Battery disconnect | 225A | 350A | 500A | 700A | 900A | 1200 | 2000 | ||||||||||||
|
| breaker |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| CB3 | STS contactor |
|
|
|
|
|
| 135A |
|
|
|
|
|
| 260A | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
| 52C | Inverter output | 135A | 200A | 350A | 450A | 450A | 660A | 910A | ||||||||||||
|
| contactor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 52S | Bypass contactor | 135A | 200A | 350A | 450A | 450A | 660A | 910A | ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| 88RC | Control circuit contactor |
|
|
|
|
|
|
| 90A |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
F | FCU, FCV, FCW | AC input fuse | 200A/660V |
|
| 250A/660V |
|
|
|
|
|
|
| 315A/660V |
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
FIU, FIV, | Inverter output fuse | 250A/660V | 200A/660V | 315A/660V | 315A/660V | 315A/660V | 315A/660V | 315A/660V | |||||||||||||
U | |||||||||||||||||||||
S |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
FUA, FUB, FUC | Control power fuse |
|
|
|
|
|
|
| 30A/600V |
|
|
|
|
|
|
| |||||
E |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
(OPTION) | Bypass input fuse | 200A/ | - | 315A/ | - | 250A/ |
| - | 250A/ |
| - | 315A/ |
| - | 315A/ |
| 315A/ |
| |||
S |
|
|
|
|
| ||||||||||||||||
FSU, FSV, FSW |
| 660V |
| 660V |
| 660V |
|
| 660V |
|
| 660V |
|
| 660V |
| 660V |
| |||
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
| FZS1, 2, 3 | Bypass input ZNR fuse |
|
|
|
|
|
|
| 16A/500V |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| FBS1, 2, 3 | Control power fuse |
|
|
|
|
|
|
| 10A/600V |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| FZR1, 2, 3 | AC input ZNR fuse |
|
|
|
|
|
|
| 16A/500V |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| FPU, FPV, FPW | Parallel control |
|
|
|
|
|
|
| 10A/600V |
|
|
|
|
|
|
| ||||
|
| circuit fuse |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|