C)Bypass Operation Procedure

MITSUBISHI

9800A SERIES UPS

ELECTRIC

OWNERS / TECHNICAL MANUAL

C)Bypass Operation Procedure

UPS

1.Check for “SYNC” on the LCD.

2.Press the "START/STOP MENU" from the LCD Main Menu.

3.Press the "STOP" key on the LCD.

**Transfer from bypass to inverter.

UPS

1.Press the "START/STOP MENU" from the LCD Main Menu.

2.Press the "START" key on the LCD.

Page Number:

3-26

Note: When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter start or stop operation can only be performed remotely. If local inverter start or stop operation is required (at the UPS), select "LOCAL" in "Remote/Local" selection in setup page. Select “LOCAL” mode for the purpose of this stop procedure.