13 - 33
13. OPTIONS AND AUXILIARY EQUIPMENT
(2) Connection diagram
RA2
EMG
SON
C
B
R/L11
Three-phase
200 to 230VAC
S/L21
T/L31

R2/L1

S2/L22
R2/L12
T2/L32

S2/L2

(Note 3)
SG
P24
SD
RDYB
RDYA
RSO
SE
A

T2/L3

R/L11
S/L21
T/MC1
RES
SD
(Note
1)
L11
RES
SG
SG
ALM
VIN
U

V

W

SG
(Note 1)
(Note1)
(Note 3)
RA1
EMG
SON
(Note 2)
RA3
RA2
RA1
RA4
24VDC
power
supply
U
V
WThermel
relay OHS2
OHS1

CN2

MC

NFB FR-CVL FR-CV

MC
RA2 RA3 RA4 EMG OFF ON
RESET
SK
MC
(Note 2)(Note 1)
Servo motor
Servo amplifier
(Note 1)

N

L21
P
P/L
P/L
P1
(Note 5)
(Note 4)

Note 1. Configure a sequence that will shut off main circuit power in the following cases:

Alarm occurred in the FR-CV or the servo amplifier.

Emergency stop is activated.

2. For the servo motor with thermal relay, configure a sequence that will shut off main circuit power when the thermal relay

operates.

3. For the servo amplifier, configure a sequence that will switch the servo on after the FR-CV is ready.

4. For 7kW or less servo amplifier, always remove the wiring (3.5kW or less: across P-D, 5k 7kW: across P-C) of built-in

regenerative brake resistor.

5. For the amplifiers of 11k to 22kW, make sure to connect across P-P1. (Wiring is factory-connected.)

(3) Wires used for wiring(a) Wire sizes1) Across P-P, N-NThe following table indicates the connection wire sizes of the DC power supply (P, N terminals)between the FR-CV and servo amplifier. The used wires are based on the 600V vinyl wires.
Total of servo amplifier capacities [kW] Wires[mm2]

1 or less 2

23.5

55.5

78

11 14

15 22

22 50