Mitsubishi Electronics PUHY-YMC English, Appropriate tightening torque by torque wrench

Models: PUHY-YMC

1 103
Download 103 pages 62.79 Kb
Page 17
Image 17
Appropriate tightening torque by torque wrench

AValve stem

[Fully closed at the factory, when connecting the piping, when evacuating, and when charging additional refrigerant. Open fully after the operations above are completed.]

BStopper pin [Prevents the valve stem from turning 90° or more.]

CPacking (accessory)

DDistributer (gas) (option)

Mount packing (accessory) securely to the valve flange so that gas does not leak. (screw tightening torque is 43 N·m (430 kg·cm). Apply a coat of refrigerating machine oil to both surfaces of the packing.

D’ Connecting pipe (accessory)

[Use packing and securely install this pipe to the valve flange so that gas leakage will not occur. (tightening torque: 25 N·m (250 kg·cm)) Coat both surfaces of the packing with refrigerator oil.]

EOpen (operate slowly)

FCap, copper packing

[Remove the cap and operate the valve stem. Always reinstall the cap after operation is completed. (valve stem cap tightening torque: 25 N·m (250 kg·cm) or more)]

GService port

[Use this port to evacuate the refrigerant piping and add an additional charge at the site.

Open and close the port using a double-ended wrench.

Always reinstall the cap after operation is completed. (service port cap tightening torque: 14 N·m (140 kg·cm) or more)]

HFlare nut

[Tightening torque: 80 N·m (800 kg·cm) ···liquid, 55 N·m (550 kg·cm) ···oil blance

Loosen and tighten this nut using a double-ended wrench. Coat the flare contact surface with refrigerator oil.]

H’ Flare nut

Tightening torque is 55 N·m (550 kg·cm). Use a double spanner to open and close. Apply a coat of refrigerating machine oil to the flare bonding surface.

Iø 38.1 (PUHY-600YSMC)

ø 44.5 (PUHY-650/700/750YSMC)

JField piping

[Braze to the connecting pipe. (when brazing, use unoxidized brazing.)]

Appropriate tightening torque by torque wrench

Copper pipe external dia. (mm)

Tightening torque (N·m) / (kg·cm)

ø 6.35

 

14 to 18

/ 140 to 180

ø 9.52

 

35 to 42

/ 350 to 420

ø 12.7

 

50 to 57.5 / 500 to 575

 

 

 

 

 

ø 15.88

 

75 to 80

/ 750 to 800

ø 19.05

 

100 to 140

/ 1000 to 1400

Tightening angle standard

 

 

 

 

 

 

Pipe diameter (mm)

Tightening angle (°)

 

 

ø 6.35, ø 9.52

60 to 90

 

 

ø 12.7, ø 15.88

30 to 60

 

 

ø 19.05

20 to 35

 

 

ENGLISH

Note:

If a torque wrench is not available, use the following method as a standard

When you tighten the flare nut with a wrench, you will reach a point where the tightening torque will abrupt increase. Turn the flare nut beyond this point by the angle shown in the table above.

Manual background Caution:

Always remove the connecting pipe from the ball valve and braze it outside the unit.

-Brazing the connecting pipe while it is installed will heat the ball valve and cause trouble or gas leakage. The piping, etc. inside the unit may also be burned.

17

Page 17
Image 17
Mitsubishi Electronics PUHY-YMC installation manual English, Appropriate tightening torque by torque wrench